FP S-Compact BB / LAN
22
Step 6: Connecting peripherals
Connecting
peripherals
Connect all cable connections intended for the application.
The connection diagram shows the interfaces available
(see page 14).
Connecting the M-Bus counter
M-Bus connection
Feed a suitable cable through the cable gland.
Connect the two cores to the terminals (MBus + / MBus -).
Tighten the clamping screws to a torque of 0.5 Nm (0.37 ft lb).
The M-Bus can be loaded with max. 10 M-Bus loads and is not
galvanically isolated. The cable length shall not exceed a total
length of 50 metres (164 ft). The M-Bus connection is short-
circuit proof.
Damage to the connection terminals due to excessive
torque!
Use a torque screwdriver.
Tighten the clamping screws to a torque of 0.5 Nm (0.37 ft lb).
Cable gland
M-Bus connection terminals