6. Commissioning
6 Commissioning
u
Observe the safety instructions. See
.
6.1
Commissioning the Ethernet Interface
For communication via the Ethernet interface, fos4X recommends the use of the
fos4X C API. See fos4X C API documentation.
6.2 Commissioning the CAN Interface
Conditions:
■
Planned Node ID for the Blackbird OECD available.
Commissioning the CAN Interface
1.
Open the web-interface. See
Opening the Web Interface., page 57
The web interface is displayed.
2.
Click on SETTINGS.
3.
fos4X recommends: Set a password. See
.
4.
fos4X recommends: Set a system name and location. See
.
5.
Set a CANopen Node ID (factory setting: 3)
6.
Set the CANopen data rate to the data rate of the CAN bus (factory setting: 500).
7.
6.3 Set or change the password.
Setting or changing the password:
1.
Open the web-interface. See
Opening the Web Interface., page 57
.
2.
If a password is set: Log in to the web interface.
3.
Open the page SETTINGS.
4.
Click on SYSTEM PASSWORD.
54 / 80
MDE0835_4-10_1.3.x_5.0_Blackbird
OECD_(6CH, CNO)-en-us
© fos4X 2020