3. Product Description
State
Device state
Description
Slow flashing
Pre-Operational
■
After booting, if
auto-
operational
is not active
■
Set by Bus-Master
Single flash
Stopped
■
Set by Bus-Master
Double flash
-
Reserved for future assignment
Error-LED
Table 21: Error-LED on the CAN Connector
State
Device state
Description
Off
-
No error
Slow flashing
Invalid
Configuration
General configuration error
Single flash
Warning limit
reached
At least one error counter of the CAN
controller has reached or exceeded the
warning level.
Double flash
Error control
event
A
guard event
master) or a
heartbeat event
(heartbeat consumer) has occured.
Triple flash
Sync error
The sync message was not received
within the configured time span for the
communication cycle
On
Bus off
Error with the connection to the CAN
controller
3.5 Software
3.5.1 Factory Settings
Table 22: Factory Settings
Parameter
Factory setting
Static
IP-address
192.168.39.99
22 / 80
MDE0835_4-10_1.3.x_5.0_Blackbird
OECD_(6CH, CNO)-en-us
© fos4X 2020