NetDAQ
Service Manual
2-62
The scale factor is derived as follows:
S = 1 - {[(16P2 - N2) - (16P0 - N0)]K2}
where
S = scale factor
P2 = P counts (both references on)
N2 = N counts (both references on)
P0 = P counts (both references off)
N0 = N counts (both references off)
K2 = (0.1) / (16) / (1843) / (1.6)
Zero Offset Readings
2-117.
There are four zero readings: one for each gain setting of the DC buffer amplifier. Zero
offset readings are similar to VDC readings, except that no channel selection is required
and no function relay switching is required. The Stallion chip must be configured. The
A/D is placed in normal measurement mode. The number of readings to average is the
same as for a normal reading (see Table 2-20: A/D Readings to Average to Obtain a
Measurement). Zero offset measurements are converted to volts in the same way as
normal channel measurements, except, of course, that no zero offset is subtracted. The
reference balance scale factor is used.
Housekeeping Schedule
2-118.
Housekeeping readings are always taken in response to a “Do Housekeeping” command
from the outguard, as described in “Do Housekeeping” earlier in this chapter.
Setting the HK bit in a configuration command causes the inguard to schedule
housekeeping readings on a rotating basis, taking one at the end of each channel scan. It
also enables a timer, which is started at the end of a scan or after a configuration
command. Whenever the timer expires, the next housekeeping reading in the schedule is
measured, and the timer is restarted. The timer is set to expire after 17.476 seconds.
On the medium and slow rate, all six housekeeping readings are scheduled as described
in the preceding paragraph. On the fast rate, however, only zero offset readings are
scheduled. This is because a single reference balance reading is longer than a normal
reading on the fast rate, which would cause scans containing them to take longer.
Self-Tests
2-119.
There are two series of self-tests performed by the inguard: those done automatically at
power-up, and those done in response to a self-test command from the outguard.
Power-Up Self-Tests
2-120.
On power-up the inguard performs a ROM checksum test and a destructive RAM test. If
either of these tests fail, the inguard treats it as a fatal error and enters the boot monitor.
No explicit indication of either of these tests failing is given to the outguard.
Summary of Contents for NetDAQ 2640A
Page 14: ...NetDAQ Service Manual x...
Page 46: ...NetDAQ Service Manual 2 4...
Page 106: ...NetDAQ Service Manual 2 64...
Page 108: ...NetDAQ Service Manual 3 2...
Page 164: ...NetDAQ Service Manual 4 42...
Page 206: ...NetDAQ Service Manual 6 2...
Page 218: ...NetDAQ Service Manual 6 14 2645A 1601 Figure 6 2 A1 Main PCA Assembly...
Page 220: ...NetDAQ Service Manual 6 16 2620A 1601 Figure 6 3 A2 Display PCA Assembly...
Page 230: ...NetDAQ Service Manual 6 26 2645A 1603 Figure 6 5 2645A A3 A D Converter PCA Assembly...
Page 234: ...NetDAQ Service Manual 7 2...
Page 242: ...2640A 2645A Service Manual 7 10 Figure 7 2 A2 Display PCA Assembly 2620A 1602...
Page 243: ...Schematic Diagrams 7 7 11 Figure 7 2 A2 Display PCA Assembly cont 2620A 1002...
Page 251: ...Schematic Diagrams 7 7 19 2645A 1603 Figure 7 4 2645A A3 A D Converter PCA Assembly 2645A 1603...
Page 258: ...2640A 2645A Service Manual 7 26 Figure 7 5 A4 Analog Input PCA Assembly 2620A 1604...
Page 260: ...2640A 2645A Service Manual 7 28...