![Fluke molbox RFM Operation And Maintenance Manual Download Page 51](http://html1.mh-extra.com/html/fluke/molbox-rfm/molbox-rfm_operation-and-maintenance-manual_2310052051.webp)
3. OPERATION
Page 41
© 1998-2007 DH Instruments, a Fluke Company
When the TARE function is activated, molbox RFM’s internal valves operate to
pneumatically connect together the two absolute transducers, and both legs of
the microrange option differential transducer if present, at the molbloc operating
pressure. The user can select whether this pressure is the upstream or
downstream molbloc pressure so that the
tare
can be made at the pressure that
will be held stable during operation (generally by a regulator or because it is
open to atmosphere). Activating the
tare
causes molbox RFM to record the
current differential as the
tare value
. The
tare value
will be used to correct all
subsequent RPT readings. For the absolute transducers the
tare value
is the
difference between the two transducer readings (hi - lo). The upstream RPT will
be corrected by (-
tare value
/2) and the downstream RPT will be corrected by (+
tare value
/2). For the microrange differential RPT, the
tare value
is the differential
value read. The differential transducer will be corrected by subtracting the
tare
value
from the current reading.
1.
High Isolation:
Open
2.
Low Isolation:
Closed
3. Bypass:
Open
4. Mirorange
Bypass:
Open
Figure 5.
molbox RFM
Internal Pneumatic Schematic – TARING, UPSTREAM molbloc-L OPERATION
OPERATION
At a minimum, the TARE function should be executed whenever the operating
pressure of the molbloc is changed significantly, at the beginning of each
test or any time a significant zero error is observed. For best results, it is
possible to
tare
before every reading since taring can be executed while
flowing. Best results will be obtained if the TARE function is executed with a
stable flow through the molbloc.
To access the TARE function press
[TARE]
,
<1tare>
.
The display is:
Select tare pressure:
1upstream 2dnstream
Selecting
<1upstream>
will
tare
the molbox RFM RPTs at the molbloc’s
upstream pressure (see Figure 5). Selecting
<2dnstream>
will
tare
the RPTs at
the molbloc’s downstream pressure (Low isolation valve open, High isolation
valve closed). Select the position where the pressure will remain the most stable
during molbloc operation.