BE6000 Ultrasonic Flow Meter O&M Manual
Flomotion Systems, Inc. ~ FlomotionSystems.com
35
Select the sources for temperature signals when measuring energy. The following 2 options are provided;
0. From AI1, AI2
1. Fixed Difference
If “Fixed Difference” is selected the value should be entered manually through keypad.
•
Specific Heat (M86)
Select one of the following 2 kinds of specific heat;
0. GB
1. Fixed Specific Heat
Normally, 0.004186 GJ/ m
3o
C(=1000 kcal/ m
3o
C). Use M+9 to check the current temperature and calorie.
•
Energy Totalizer Switch (M87)
Turn on/off the energy totalizing function.
•
Energy Totalize Multiplier (M88)
Select the energy totalize multiplier. 10
-4
– 10
6
(E-4 – E-6)
•
Reset Energy Totalize (M89)
Select YES to reset energy accumulation.
•
Signal Strength and Signal Quality (M90)
Display the measured signal strength and signal quality Q value upstream and downstream. Signal strength
is indicated from 00.0~99.9. A reading of 00.0 indicates no signal detected, while 99.9 indicates maximum
signal strength. Normally the signal strength should be > 60.0. Signal Quality Q is indicated 00~99.
Energy Totalizer ON/OFF
ON
Energy Multiplier [88
4. xl
SQuality [90
UP:00.0 DN:00.0 Q=00
Reset Energy Totalize
NO
Specific Heat Select
0.0041868 GJ/m
3o
C
Temperature Select
0. From AI1, AI2