BE6000 Ultrasonic Flow Meter O&M Manual
Flomotion Systems, Inc. ~ FlomotionSystems.com
30
•
Date and Time Settings(M60)
Date and time modifications are made. The format for setting time setting is 24hours. Press ENT, wait until
“>” appears. The modification can then be made.
•
ESN(M61)
Displays the electronic serial number (ESN) of the instrument. This ESN is the only one assigned to each
BE6000 series flow meter ready to leave the factory. The factory uses it for files setup and for management
by the user.
•
Serial Port Setup(M62)
To set RS232 port property. The first information is bit rate and can be 110, 150, 300, 600, 1200, 240, 4800
or 9600. The second information is data bit and it can be either 7 or 8. The third information is parity and can
be either None, Even or Odd. And the fourth information is stop bit and can be 1, 1.5 or 2.
•
AI1 Range(M63)
To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the
value 10 in the above box represents 4mA and 100 20mA.
•
AI2 Range(M64)
To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the
value 10 in the above box represents 4mA and 100 20mA.
•
AI3 Range(M65)
To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the
value 10 in the above box represents 4mA and 100 20mA.
AI Value Range [65
10-100
AI Value Range [64
10-100
AI Value Range [63
10-100
RS-232C Setup [62
9600, 8, None
Ultrasonic Flowmeter
ESN = 35800003
YY-MM-DD HH:MM:SS
04-05-05 11:05:05