BE6000 Ultrasonic Flow Meter O&M Manual
Flomotion Systems, Inc. ~ FlomotionSystems.com
23
Select one of the transducer mounting types from the list provided;
0. V Method
2. N Method (for small pipes)
1. Z Method
3. W Method (for very small pipes)
•
Transducer Distance(M25)
This window is only for display of the transducer mounting distance that was calculated based on the
parameters input in the foregoing menus. The distance is between the front edges of the transducers.
•
Parameter Save/Load(M26)
The pipe parameter data can be saved and loaded for a quick set up. A total of 18 sets of setup data can be
stored and loaded. The following menus are provided;
0. Entry SAVE
1. Entry LOAD
2. Browse
When 0 is pressed and then ENTER is pressed, the window will show the address number and the data
stored in that address. The data can be browsed using up and down keys and edited. Press ENTER to save
the data. If a set of parameter data is loaded, the system will calculate the parameters and show the sensor
distance in M25 window.
•
Current Section Area(M27)
The section area of the flow will be displayed.
•
Data Holding(M28)
Select “Yes” to hold the last good flow signal displayed if the flow meter experiences a poor signal condition.
This function will allow continued data calculation without interruption.
•
Empty Pipe Setup(M29)
This value is used to solve the problem of the empty pipe. Even when the pipe is empty, the flow meter will
show “Normal Working” for the signals that are transmitted and reflected through the pipe wall. In order to
Empty Pipe Setup
0
Current Section Area
1963.5 mm2
Parameter Setups
0.
Entry SAVE
Transducer Spacing
50.00mm
Holding With Poor Signals
Yes