Chapter 3: Installing the FT-70
3-27
Example B: Using a Voltage Regulating Transformer
If voltage stability is a problem, a voltage regulating type trans-
former should be used. This example uses a transformer to isolate
the FT-50 and to convert the line voltage to the proper voltage for
the FT-70.
1.
The secondary side of the transformer must be connected to the
hot and neutral wires in the FT-70. It makes no difference
which wires from the secondary attach to input wires in the
FT-70, but if color coded wires are used, connect white to
neutral.
2.
Do not connect the transformer secondary terminals to the
neutral on the primary because it negates the isolation
properties.
3.
Connect the FT-70 ground stud to the facilities ground system.
The neutral wire should also be connected to this ground stud.
4.
If the transformer has an internal electrostatic shield, ground it
to the Earth ground if possible (however the FT-70 ground is
suitable). This shield may be attached to the transformer case
in some units, or it may have a separate wire lead. Examine the
transformer carefully to determine if it is shielded and, if so,
ground the shield.
Figure 3-25.
Main power wiring Example B.
115, 23O,
440, etc.
1Ø
115/230 VAC
6
4
1
115
230
2
3
N
7
8
9
10
H
5
No.
Description
1
FT-70 Power Junction Box
2
Voltage Switch Proper Voltage
3
Connect FT-70 pigtail leads to
input power wires
4
FT-70 Ground Stud
5
External Breaker or Disconnect
6
Separate Transformer
7
White
8
Blue
9
Black
10
Brown
Industrial Dynamics Company, Ltd. ©
Form
40256-0600
Summary of Contents for FT-70c
Page 1: ...FT 70c Service and Technical 40256 0600 Reference Manual for Can Inspection...
Page 14: ...Table of Contents XIII Industrial Dynamics Company Ltd Form 40256 0600...
Page 21: ...FT 70 Fill Level Inspector Service Manual 1 2 Industrial Dynamics Company Ltd 40256 0600...
Page 33: ...FT 70 Fill Level Inspector Service Manual 1 14 Industrial Dynamics Company Ltd 40256 0600...
Page 35: ...FT 70 Fill Level Inspector Service Manual 2 2 Industrial Dynamics Company Ltd 40256 0600...
Page 39: ...FT 70 Fill Level Inspector Service Manual 2 6 Industrial Dynamics Company Ltd 40256 0600...
Page 41: ...FT 70 Fill Level Inspector Service Manual 3 2 Industrial Dynamics Company Ltd 40256 0600...
Page 69: ...FT 70 Fill Level Inspector Service Manual 3 30 Industrial Dynamics Company Ltd 40256 0600...
Page 71: ...FT 70 Fill Level Inspector Service Manual 4 2 Industrial Dynamics Company Ltd 40256 0600...
Page 139: ...FT 70 Fill Level Inspector Service Manual 5 44 Industrial Dynamics Company Ltd 40256 0600...
Page 141: ...FT 70 Fill Level Inspector Service Manual 6 2 Industrial Dynamics Company Ltd 40256 0600...
Page 183: ...FT 70 Fill Level Inspector Service Manual 7 2 Industrial Dynamics Company Ltd 40256 0600...
Page 225: ...FT 70 Fill Level Inspector Service Manual 9 2 Industrial Dynamics Company Ltd 40256 0600...
Page 233: ...FT 70 Fill Level Inspector Service Manual 10 2 Industrial Dynamics Company Ltd 40256 0600...
Page 243: ...FT 70 Fill Level Inspector Service Manual 10 12 Industrial Dynamics Company Ltd 40256 0600...