2. Installation and interfaces
2-15
Festo P.BE-CTEU-DN-OP+MAINT-EN en 1206NH
2. Set the baud rate: when setting the baud rate, take into
account the length of the network lines (main bus line,
branch lines and branches)
see note below.
Note
Maximum effective data rate (baud rate)
The setting of the baud rate depends on the length of all
fieldbus connecting cables (network lines).
•
Consider the length of the fieldbus line between the PLC
and bus node (main bus line) as well as the length of any
existing branch lines and branches for continued field-
bus configuration.
•
Also consider the overall length (sum) of all branch lines.
•
The table below contains reference values for the max-
imum baud rate, depending on the line lengths. The
baud rates named here are not supported by all control-
lers.
•
Observe any deviating specifications in the manual of
your control system or network scanner.
•
Further information can be found in the specifications of
the ODVA
www.odva.org.
Max. data rate (baud rate)
dependent on the line length (reference values)
Main bus
line
(Trunk line)
Branch line
(Drop line)
Baud rate
Individual branch line
All branch lines
(total)
Max. 100 m
Max. 6 m
Max. 39 m
500 kBaud
Max. 250 m
Max. 6 m
Max. 78 m
250 kBaud
Max. 500 m
Max. 6 m
Max. 156 m
125 kBaud
Tab. 2/8:
Maximum data rate (baud rate)
Summary of Contents for CTEU-DN
Page 2: ......
Page 15: ...Introduction 1 1 Festo P BE CTEU DN OP MAINT EN en 1206NH Chapter 1 Introduction...
Page 22: ...1 Introduction 1 8 Festo P BE CTEU DN OP MAINT EN en 1206NH...
Page 44: ...2 Installation and interfaces 2 22 Festo P BE CTEU DN OP MAINT EN en 1206NH...
Page 57: ...Commissioning 4 1 Festo P BE CTEU DN OP MAINT EN en 1206NH Chapter 4 Commissioning...
Page 76: ...4 Commissioning 4 20 Festo P BE CTEU DN OP MAINT EN en 1206NH...
Page 77: ...Diagnostics 5 1 Festo P BE CTEU DN OP MAINT EN en 1206NH Chapter 5 Diagnostics...
Page 90: ...5 Diagnostics 5 14 Festo P BE CTEU DN OP MAINT EN en 1206NH...
Page 91: ...Error handling 6 1 Festo P BE CTEU DN OP MAINT EN en 1206NH Chapter 6 Error handling...
Page 98: ...6 Error handling 6 8 Festo P BE CTEU DN OP MAINT EN en 1206NH...
Page 99: ...Technical appendix A 1 Festo P BE CTEU DN OP MAINT EN en 1206NH Appendix A Technical appendix...
Page 124: ...A Technical appendix A 26 Festo P BE CTEU DN OP MAINT EN en 1206NH...
Page 125: ...Index B 1 Festo P BE CTEU DN OP MAINT EN en 1206NH Appendix B Index...
Page 126: ...B Index B 2 Festo P BE CTEU DN OP MAINT EN en 1206NH Contents B Index B 1...
Page 130: ...B Index B 6 Festo P BE CTEU DN OP MAINT EN en 1206NH...