1. Installation
1−12
Festo P.BE−CPX−FB32−EN en 0605NH
1.3
C
o
nnectin
g
t
h
e
Et
h
e
r
net
f
ie
ld b
us
1.3.1
Ethernet cable
Pl
ease
n
o
te
If installation has not been carried out correctly and if high
baud rates are used, data transmission errors may occur
as a result of signal reflections and attenuations.
Causes of the transmission faults may be:
incorrect screening/shield connection
branches
transmission over long distances
unsuitable cables.
Observe the cable specifications. Refer to your controller
manual for information on the type of cable to be used.
Cable specification
Screened flexible Ethernet round cable of category 5
Max. outer diameter:
5.4 mm
Core diameter:
0.89 ... 1.0 mm AWG24−26
User−made:
plug screwed on,
type NECU−M−S−D12G4−C2−ET,
part no. 543109
Pl
ease
n
o
te
If the CPX terminal is fitted onto the moving part of a
machine, the field bus cable on the moving part must be
provided with strain relief. Please observe also the relevant
regulations in EN60204 part 1.
The specifications for Ethernet networks as per ANSI/TIA/
EIA−568−B.1 apply for the field bus length.
Summary of Contents for CPX-FB32
Page 2: ......
Page 8: ...Contents and general instructions VI Festo P BE CPX FB32 EN en 0605NH...
Page 16: ...Contents and general instructions XIV Festo P BE CPX FB32 EN en 0605NH...
Page 17: ...Installation 1 1 Festo P BE CPX FB32 EN en 0605NH Chapter 1...
Page 35: ...Commissioning 2 1 Festo P BE CPX FB32 EN en 0605NH Chapter 2...
Page 68: ...2 Commissioning 2 34 Festo P BE CPX FB32 EN en 0605NH...
Page 69: ...Diagnosis 3 1 Festo P BE CPX FB32 EN en 0605NH Chapter 3...
Page 86: ...3 Diagnosis 3 18 Festo P BE CPX FB32 E N en 0605NH...
Page 87: ...Technical appendix A 1 Festo P BE CPX FB32 EN en 0605NH Appendix A...
Page 91: ...Ethernet IP Objects of the CPX FB32 B 1 Festo P BE CPX FB32 EN en 0605NH Appendix B...
Page 131: ...Index C 1 Festo P BE CPX FB32 EN en 0605NH Appendix C...
Page 132: ...B Index C 2 Festo P BE CPX FB32 EN en 0605NH Contents C Index C 1...