background image

Faithtech

Ultra-high-power Electronic Load

User’s Manual

(

FT68200 Series

)

©Copyright Faithtech

Version V2.0

2021-06

Summary of Contents for FT68200 Series

Page 1: ...Faithtech Ultra high power Electronic Load User s Manual FT68200 Series Copyright Faithtech Version V2 0 2021 06...

Page 2: ...iod Faithtech will provide free repair for all faults in the normal usage and maintenance of the product The user need prepay one way freight for sending the product to the service department The retu...

Page 3: ...reliable grounding otherwise it may cause injury to or death of personnel and other potential electric shock hazards Operators are not allowed to open the shell of the load Non professionals are not a...

Page 4: ...tory Date Version Amendment 2020 6 1 0 Initial version 2020 9 1 01 Add functions 2020 12 1 02 Adjust overpower loading 2021 03 1 03 Dimension revision for 36kW or above 2021 05 1 04 Add appendix B 202...

Page 5: ...fication 30kW 15 1 4 8 Performance Specification 36kW 16 1 4 9 Performance Specification 42kW 17 1 4 10 Performance Specification 48kW 18 1 4 11 Performance Specification 54kW 19 1 4 12 Performance Sp...

Page 6: ...3 19 OCP Test 53 3 20 OPP Test 55 3 21 Battery Internal Resistance Test 56 3 22 Load Effect Test 58 3 23 LED Test 59 3 24 Dynamic SWEEP 62 3 25 Compound Modes CV CC CR CC CP CC 63 3 26 Parallel 64 3 2...

Page 7: ...h Technology its high performance high precision and high reliability have become the industry benchmark 1 2 Features Power density up to 6kW 3U Voltage range 150V 600V 1200V Current range 100A kW 150...

Page 8: ...ration Manual 2 monitoring capability TFT color LCD screen Chinese English menua interface Standard RS232 RS485 LAN USB serial optional GPIB or CAN interface Support SCPI Modbus CANopen protocol 1 3 D...

Page 9: ...Faithtech FT68200 Operation Manual 3 1 3 2 7U 8kW 10kW 12kW...

Page 10: ...Faithtech FT68200 Operation Manual 4 1 3 3 11U 14kW 16kW 18kW...

Page 11: ...Faithtech FT68200 Operation Manual 5 1 3 4 14U 20kW 22kW 24kW...

Page 12: ...Faithtech FT68200 Operation Manual 6 1 3 5 20U 30kW 36kW...

Page 13: ...Faithtech FT68200 Operation Manual 7 1 3 6 26U 42kW 48kW...

Page 14: ...Faithtech FT68200 Operation Manual 8 1 3 7 32U 54kW 60kW...

Page 15: ...250 0 053 286 0 53 1429 0 186 1000 1 86 5000 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 6000W 6000W 6000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2...

Page 16: ...04 214 0 4 1071 0 139 750 1 39 3750 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 8000W 8000W 8000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2 F S Dyna...

Page 17: ...0 032 171 0 32 857 0 112 600 1 12 3000 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 10000W 10000W 10000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2 F...

Page 18: ...0 027 143 0 27 714 0 093 500 0 93 2500 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 12000W 12000W 12000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2 F S...

Page 19: ...0 018 95 0 18 476 0 062 333 0 62 1667 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 18000W 18000W 18000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2 F S...

Page 20: ...3 0 013 71 0 13 357 0 046 250 0 46 1250 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 24000W 24000W 24000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2 F...

Page 21: ...02 63 0 011 57 0 11 286 0 037 200 0 37 1000 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 30000W 30000W 30000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0...

Page 22: ...63 0 009 50 0 09 250 0 031 167 0 31 833 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 36000W 36000W 36000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2 F...

Page 23: ...63 0 009 50 0 09 250 0 027 143 0 27 714 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 42000W 42000W 42000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2 F...

Page 24: ...2 63 0 009 50 0 09 250 0 023 125 0 23 625 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 48000W 48000W 48000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2...

Page 25: ...2 63 0 009 50 0 09 250 0 021 111 0 21 556 Accuracy Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Vin Rset 0 2 0 2 IF S Constant Power Range 54000W 54000W 54000W Accuracy 0 2 0 2 F S 0 2 0 2 F S 0 2 0 2...

Page 26: ...olution 0 5mV 2 5mV 2mV 10mV 4mV 20mV Accuracy 0 025 0 025 F S 0 025 0 025 F S 0 025 0 025 F S Constant Resistance Range 0 002 13 0 02 63 0 009 50 0 09 250 0 019 100 0 19 500 Accuracy Vin Rset 0 2 0 2...

Page 27: ...ssory Explanation Accessory Qty Explain Power cord 1 PCS For 220VAC INPUT RS232 cable 1 PCS Connect PC LAN cable 1 PCS Connect PC or use for master slave parallel User s Manual 1 PCS Installing and op...

Page 28: ...2 2 2 Front Panel 1 Power Switch Keyboard 2 Model sticker Rotary knob 3 Color TFT screen 2 3 Keyboard Key function description Key Function Description Constant Current Constant Voltage Constant Resis...

Page 29: ...Numeric key can perform the second function when combined with Shift key Decimal Point Cursor left movement Cursor right movement Confirm key Exit key Starts loading unloading Key Function description...

Page 30: ...nk Short circuit disabled Input Off input off On input on Compound function Shift key second function blank key original function V I Readback Data Display This area usually displays readback voltage...

Page 31: ...minal S Positive end of remote V sense S negative end of remote V sense 2 Analog ports for parallel 3 External analog programming input 4 Current monitoring output 5 Communication ports for parallel 6...

Page 32: ...re that the air inlet and outlet of the electronic load keep a clearance of more than 1 meter with other objects to facilitate air circulation Do not place objects weighing more than 40kg on the elect...

Page 33: ...put connection WARNING In order to comply with safety regulations the input wiring of the electronic load must be able to withstand the maximum short circuit current connected to the DUT without overh...

Page 34: ...When the load is working the input current will produce a certain voltage drop on the contact resistance between the port and the wire which will affect the voltage measurement accuracy of the load It...

Page 35: ...current and load power FT68200 series allow for master slave parallel operation of up to 10 identical loads As shown in the figure above three types of cables are needed for paralleling 1 Use thicker...

Page 36: ...gh the front panel keyboard The LCD screen provides users with display functions such as parameter viewing measurement display and status indication Some parameters can only be set in local mode inclu...

Page 37: ...ge Figure 3 2 CC Mode Switch Current Range CC mode has two ranges low range and high range The low range provides better resolution at low current setting while high range provides high current loadin...

Page 38: ...et to non zero values the current setting range in constant current mode is limited between the upper current limit and the lower current limit This function can prevent user misoperation and protect...

Page 39: ...to change the voltage value or press number key to input voltage value finally press Enter key again to validate the input Set the Electronic Load Response Speed Constant voltage mode has two types of...

Page 40: ...ch to CR mode Figure 3 5 CR Mode In CR mode the load will sink a resistance in accordance with the programmed value regardless of the input voltage Figure 3 6 CR Mode CR mode has only one range CR is...

Page 41: ...the lower limit This function can prevent user misoperation and protect the device under test 1 Press Menu to go to main menu 2 Select Set Limit sub menu press to go to limit setting pape 3 Select R_...

Page 42: ...function can prevent user misoperation and protect the device under test 1 Press Menu to go to main menu 2 Select Set Limit sub menu press to go to limit set page 3 Select P_MAX and P_MIN to set the d...

Page 43: ...ger signal Figure 3 10 CONT Mode 1 Set Way as CONT 2 Set CC 1 and CC 2 3 Set Width 1 and Width 2 setting range 0 01 60000ms 4 Set Slew UP and Slew DN unit A us 5 Press to start test PULS Mode Pulse In...

Page 44: ...GG Mode 1 Set Way as TOGG 2 Set CC 1 and CC 2 3 Set Slew UP and Slew DN unit A us 4 Press to start test 5 Press to generate trigger signal in order to switch between CC 1 and CC 2 3 4 Slew rate and mi...

Page 45: ...Input Control After the load is powered on it is in an unloaded state and the input switch of the load can be controlled by the keys on the front panel key is lighted on indicating that the input is t...

Page 46: ...ggle mode press the button to short circuit and then press the button again to disable short circuit In the Hold mode press and hold the key to short circuit and release the key to exit the short circ...

Page 47: ...p after it is turned on ON Input Set to off the input is turned off when power on when set to on and turn on Power Save the load will automatically turn on the input when power on APG Turn on off exte...

Page 48: ...upper limit for constant voltage operation V_MIN Voltage lower limit for constant voltage operation I_MAX Current upper limit for constant current operation I_MIN Current lower limit for constant curr...

Page 49: ...external trigger signal input terminal Just set EXT S in Set APG sub menu to Trigger apply a low pulse to the INHIBIT terminal and the load will perform a trigger operation Bus trigger after the load...

Page 50: ...use it may damage the load if the input voltage slope is too high 3 To use Voff function first set Von as Non zero value Voff as Non zero value also and make sure Von Voff 3 11 Current Limit The curre...

Page 51: ...erminals of the DUT respectively to eliminate the voltage drop on the wire thereby obtaining a higher measurement accuracy Operation Procedures 1 Press Menu to go to main menu 2 Select Set APG press t...

Page 52: ...with the help of an external digital voltmeter or oscilloscope 3 14 Analog Programming There is a galvanically isolated terminal located on the rear of the device It offers analog inputs to set load c...

Page 53: ...s and save costs for users Operation Procedures 1 Press Menu to go to main menu 2 Select Set APG press to pop up application set page 3 Set PoweDoub item as ON To ensure safe and normal operation of i...

Page 54: ...provides the option of OVP for users to set and use For related configuration refer to the protection setting in Set Menu Configuration Set to 0 means to turn off the software over voltage protection...

Page 55: ...ggered and the screen will prompt OT Reverse Voltage Input Protection When the input voltage polarity is reversed the input reverse connection protection will be triggered and the screen will prompt R...

Page 56: ...e step running time The sequence single step time range is 0 0001 99999s Sequence support cycle times and linked files Cycle The number of cycles that the sequence file runs ranging from 0 to 60000 ti...

Page 57: ...rsor moves to Step Time 9 Set Step Time press to confirm cursor move to SEQ Step and increase the figure by 1 10 Repeat the process of 7 untill all operations are completed 11 Press Save to save the s...

Page 58: ...ed to discharge super capacitors The discharge test supports 3 discharge modes CC CR and CP During the discharge process the load measures its discharge power unit AH discharge energy unit WH and disc...

Page 59: ...Step test once accumulated discharge time reaches this figure 3 19 OCP Test The load has an over current test function OCP and its measurement principle is when the input voltage reaches the turn on...

Page 60: ...the end voltage 6 Press to view the P Max Volt and Curr corresponds to the overcurrent point Parameter Explanation Name Explain Von Volt OCP test turn on voltage Von Delay Delay load time after the in...

Page 61: ...test The FT68200 series load provides the OPP power judgment function which can judge the range of the measurement result and report PASS or FAIL Operation Procedures 1 Press Test to go to Test functi...

Page 62: ...ops and the screen displays ERROR 3 21 Battery Internal Resistance Test The load uses the DC discharge method to measure the internal resistance of the battery According to Ohm s law R U I the load ca...

Page 63: ...upper limit or the lower limit of judgment If the judgment upper limit or judgment lower limit is set to 0 it means that no inspection will be performed and PASS will be prompted directly Parameter E...

Page 64: ...s according to the following formula V VI_MIN VI_MAX Regulation V VI_Normal Rs V I_ MAX I_MIN Operation Procedures 1 Press Test to go to Test function selection 2 Rotate the knob to select LOEF press...

Page 65: ...or LED power supply test The electronic load is controlled to simulate the voltage and current waveforms of the real LED load Before using the LED test function the user needs to understand the workin...

Page 66: ...s of the LED referred to as the VI curve of the LED The following is the VI curve of a certain brand LED Figure 3 28 VI Curve of A Branded LED Through its VI characteristic curve we can know that the...

Page 67: ...stance coefficient of multiple LEDs in series circuit is equal to that of single LED Therefore the led internal resistance coefficient can be calculated through the VI curve of LED as well as LED work...

Page 68: ...urrent frequency captures and records the peak voltage Vp valley voltage Vp and its corresponding frequency points of the tested power supply during the whole testing process The dynamic sweep functio...

Page 69: ...compound operation mode is to add CC current limit setting in the CV CR CP static mode which can help engineers effectively solve the problem of excessive instantaneous current during test and protec...

Page 70: ...Figure 3 32 Compound Operation Modes 3 Configure compound modes parameters 4 Press to start test 3 26 Parallel FT68200 supports master slave parallel operation of up to 10 identical units the maximum...

Page 71: ...el analog cable to connect the ANALOG terminal the parallel analog cable needs to be purchased separately 4 Use thicker wires to connect the load and the device under test 5 After completing the wirin...

Page 72: ...capture functions are used to measure the highest and lowest values of the input voltage during loading The principle is from the input On to the input Off during this period of time the load constan...

Page 73: ...asurement signal as rising or falling The principle of time measurement is from the initiation of time measurement the load constantly detects the input signal When the signal meets the direction and...

Page 74: ...nd End TRIG can be set as Volt voltage or Curr current or Ext external level signal 4 Beg DIRE and End DIRE can be set as Rise or Fall 5 Set the start main value Beg LEVL and end main value End LEVL t...

Page 75: ...n the turn on of time measurement and load input When measuring the external level there is no need to set the start main value Beg LEVL or the end main value End LEVL just select the level direction...

Page 76: ...umber 1 press to confirm thus save CC 10A to position 1 4 Switch to CV mode and set the voltage to 30V 5 Press Save to enter into save interface 6 Input number 2 press to confirm thus save CV 30V to p...

Page 77: ...l be initialized to the default parameters 1 Press Menu to go to main menu 2 Select System Others sub menu press 3 Set Power Save to ON so as to turn on power down save function When the power down sa...

Page 78: ...OGG mode the trigger signal can switch the load current in the automatic test function the trigger signal can switch the running step to the next step Toggle As the input switch control signal The inp...

Page 79: ...e FT68200 series load provides an OUT output signal port on its rear panel This port outputs a TTL level signal and its function is as follows In the automatic test function when the test result is PA...

Page 80: ...ge After running all the test steps the final result PASS or FAIL is given The automatic test function can significantly improve the detection efficiency 4 1 Edit Auto Test File The FT68200 series loa...

Page 81: ...if CR mode is selected then cursor moves to next step R Set if CP mode is selected then cursor moves to next step P Set 8 Set the current value or voltage or resistance or power press to confirm curso...

Page 82: ...is completed press to confirm cursor moves to Auto Step and increse the step number by 1 automatically 13 Repeat 6 12 untill the auto test file is completed 14 Press Save to save auto test file Note E...

Page 83: ...and whether the tested power supply is disconnected from the load after the test is completed and automatically starts the test without operating the keyboard Parameter Explanation Name Explain Volt...

Page 84: ...munication set 3 IP default 192 168 1 123 S Mask default 255 255 255 0 Ensure that electronic load IP and power supply IP in the same network segment 4 Baud default to 9600 optional 4800 19200 38400 1...

Page 85: ...nition Function 1 N C 2 RxD Receive 3 TxD Send 4 DSR 5 GND Ground 6 DTR 7 CTS 8 RTS 9 N C 5 2 2 RS485 and CAN Table 5 3 RS485 and CAN ports Table 5 2 RS485 and CAN signal definition No Definition Func...

Page 86: ...ithtech FT68200 Operation Manual 80 5 2 3 USB serial Figure 5 4 USB serial port Table 5 2 USB signal definition No Definition Function 1 VCC Power source 2 GND Ground 3 D Data negative 5 D Data positi...

Page 87: ...fter sales Overpower Protection OPP Load power exceeds set Decrease loading or increase OPP setting Overcurrent Protection OCP Load current exceeds set Decrease loading or increase OCP setting Overvol...

Page 88: ...performance version A Economical version E Static CCH Static CCL Static CVH Static CVL Static CR Static CP Dynamic CCDH Dynamic CCDL Dynamic CRD Dynamic CPD Sequence SEQ AUTO OCP OPP Discharge Test L...

Page 89: ...voltage to the electronic load all at once FUSE First calculate how much current to discharge and select the appropriate fuse Note The SPST must be in the OFF state before wiring Operation procedures...

Reviews: