Powering the modules.
Power the RIOR modules with a 24 V DC class III power supply that does not exceed the
limits for SELV/PELV.
Power supply requirements.
If the supply cable is longer than 10 meters, some protection element must be installed at the input
of the device to protect it against voltage peaks.
The power supply must be connected to the ground/shield of the module for functionality or
electromagnetic compatibility; for electromagnetic compatibility, this connection must only be done at
one point.
Nominal voltage.
Meets EN 61131-2
24 V DC
Voltage range (mean value).
Within 20.4 V DC and 28.8 V DC.
Voltage range (dynamic).
Within 18.5 and 30.2 V DC.
Voltage ripple peak-to-peak.
5% (unfiltered 6-pulse rectification).
Startup time after power-up.
Any.
Non-periodic over-
voltages.
Over-voltage.
35 V
Duration of the over-voltage.
500 ms
Recovery time.
50 s
Events per hour.
10
Transient voltage
interruptions.
Idle time.
3 ms
Recovery time.
10 s
Events per hour.
10