E145
27
732784 - Rev. A
ENGLISH
Display
Advanced Function
Default
o 1
OUT 1
:
You can set the output OUT1 (open collector N.O.) in one of the following
functions:
00
= always active
0 1
= FAIL-SAFE
02
= INDICATOR LIGHT (
off
= closed;
on
= during opening and open/
in pause;
flashing
= during closing)
03
= COURTESY LIGHT (stays on for the duration of the movement
(even in SETUP) in addition to the set time of function
t1
04
= ACTIVE ERROR
05
= automated system OPEN or in PAUSE
06
= automated system CLOSED
07
= automated system MOVING
08
= automated system in EMERGENCY
09
= automated system in OPENING
10
= automated system in CLOSING
1 1
=
DISABLED
12
= safety device ACTIVE
13
= TRAFFIC LIGHT function (active when OPENING and with automated
system OPEN)
14
= timed output which can be activated from the second radio channel
OMNIDEC
(see function
t1
)
15
= output which can be activated from the second radio channel
OMNIDEC
(step-by-step function)
16
= active during movement of leaf 1
17
= active during movement of leaf 2
If
tr
is displayed, it indicates that the output is used as a TIMER
set from the PC/MAC software.
00
t1
OUT 1 TIMING
(visualised only with the function
o1
=
03
or
o1
=
14
):
You can adjust the timing of OUT 1 output if a timed function has been selected
with a time from
1
to
59
minutes in 1-minute steps for functions 03-14 and
from
1
to
59
sec in 1-second steps for function 11
02
o2
OUT 2:
You can set the output OUT2 (open collector N.O.).
See the options as
o1
.
02
t2
OUT 2 TIMING
(visualised only with the function
o2
=
03
or
o2
=
14
):
Adjustable as for
t1
.
02