EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
83
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
55-63
Reserved
64
Operation
check
Sound indication for unit’s operating states:
1 – active (factory/default setting)
0 – inactive
65
Overriding switching to the BYPASS mode:
1 – overriding switching activated
0 – overriding switching inactive
66
Switching on the operation as a UPS:
1 – UPS active
0 – ups in the SUSPENDED/STOP mode.
67
Command for the UPS unit to switch to the WAITING mode:
1 – command for the UPS unit to switch to the WAITING mode (with battery used); the command
will be accepted only during battery-based backup operation
0 – after the command for the UPS unit to switch to the WAITING mode has been executed,
resetting effected by the UPS; also the state after the UPS unit has been initialised on start
68
Keypad lock:
1 – activated
0 – inactive
69
Initialising (calling) a battery test:
1 – Initialising a test
0 – Last initialised test completed
70
Remote activation of the output emergency off (EPO):
1 – EPO emergency mode activated
0 – EPO emergency mode deactivated
71
Cancelling the rectifier emergency states:
1 – cancelling activated
0 – cancelling deactivated
72
Cancelling the inverter emergency states:
1 – cancelling activated
0 – cancelling deactivated
73
Enforced ECO mode operation:
1 – overriding switching activated
0 – overriding switching inactive
74
Temporarily disabling of the EPO functionality:
1 – functionality disabled
0 – functionality enabled
75
Activation of the correctness check for the bypass line:
1 – functionality enabled
0 – functionality disabled
76-79
Reserved
80
Schedule Planner ON – OFF
2. Command: 0x04 (read input registers)
Register
Variable
Description
0
Type
Product identification (the UPS model range, encoded using a binary
code)
1
ApparentPower
Apparent power transmitted by the unit, encoded using a binary code
in hundreds of VA
2
ActivePower
Active power transmitted by the unit, encoded using a binary code
in hundreds of W
3
SoftwareVersion
Software version and build number (code)
MSB – firmware version, encoded using the BCD code
LSB – firmware build, encoded using binary code, where e.g. 0x1106
represents v1.1 b06
4
HardwareVersion
Hardware (equipment) version:
MSB – hardware platform revision, quoted using the following code:1 →
A, 2 → B, 3 → C, etc.
LSB – version of the hardware platform, quoted using a binary code; eg.
“0x0103” represents rev. A v. 03
5
Version CommunicationProtocol
Version and build number of the communication protocol
MSB – protocol version, encoded using the BCD code
LSB – protocol build, encoded using binary code, where e.g. 0x1106
represents 1.1 b. 06
6-15
Reserved
16
ModeOfOperation
UPS mode of operation reference number
17
Messages 1
UPS operation mode information states
18
Messages 1
United informative modes of operation UPS in parallel system
19
Alarms
UPS operation mode emergency states
20
Temperature0
Radiator temperature quoted with the resolution accuracy of one Celsius.
Summary of Contents for W/PGRLTO-3310K0/00