HA243821
Issue 5 Mar 98
Section5
Page 5 - 9
MODEL 346 INSTALLATION AND OPERATION MANUAL
5.2 TOTALISER CONFIGURATION (Cont.)
OUTPUT COUNTER ENABLE
TT1 Cntr. Out
On
The up/down arrow keys to turn the optional totaliser counter output ON or OFF.
OUTPUT SCALING
TT1 Out. Fact
The ENTER key is operated to gain access the output factor mantissa and exponent editing pages The output can
be scaled by the output factor to count at a different rate from that at which the totaliser counts. The maximum rate
for this trigger is 8 pulses per second, and each trigger pulse is “ON” for 50 milliseconds. Refer to the totalisation
factor (above) for a description of this type of ‘powers of 10’ factor.
As with the normal totalisation factor previously described, the mantissa and exponent portions of the factor are
entered on separate pages, by means of the up/down/side arrow keys.
DESCRIPTOR
TT1 Tot. Desc.
DESCRIPTOR
The totaliser descriptor is a 16-character (max.) string which appears above the counter value in background
totaliser displays and is also printed on the chart along with the totaliser count. The descriptor is entered using the
up/down/side arrow keys.