HA243821
Issue 5 Mar 98
Section5
Page 5 - 61
MODEL 346 INSTALLATION AND OPERATION MANUAL
C
Select
retransmission
output number
Select source
for this output
Select output
type
Enter measured
value which is to
be o/p low limit
(e.g. 0 mA).
Enter measured
value which is to
be o/p high limit
(e.g. 20 mA).
Any channel
(measuring or derived)
0 to 20mA, 4 to 20mA
5.8.3 RETRANSMISSION OPTION CONFIGURATION PAGES (Cont.)
Figure 5.8.3 Re-transmission configuration menu arrangement
5.8.4 CALIBRATION
INITIAL SET-UP
For the channel concerned:
a. Connect ‘V’ re-transmission terminal to the input channel’s ‘+’ terminal
b. Connect ‘C’ re-transmission terminal to the input channel’s ‘-’ terminal
c. Connect re-transmission terminals ‘I’ and ‘V’ together using a short link or jumper.
Note... The above steps must be carried out before the calibration is started, or the calibration process will fail.
CALIBRATION
Referring to section 6.3 as necessary, access the ‘Cal Retrans’ calibration page. Select the relevant re-transmis-
sion output and operate the ENTER key.
After the calibration of the first output is complete, this process can be repeated for any further re-transmission
channels, wiring each one in turn to channel one, before operation of the ENTER key for that output.