HA243821
Issue 5 Mar 98
Annex A
Page A - 27
MODEL 346 INSTALLATION AND OPERATION MANUAL
A15.0 RETRANSMISSION CONFIGURATION
Figure A15.0 Retransmission option configuration menu arrangement
DISPLAY
SCROLLABLE VALUES
DESCRIPTION OF PARAMETER OR FUNCTION
Source
1 to 9
Allows any input or derived channel to be selected for retransmission.
Output type
0 to 20mA, 4 to 20 mA
Allows one of two input ranges to be selected. The selected current
range is available either as a current or as a voltage signal according
to how the output is wired. See section 5.9 for details.
Low limit
None
Allows a value (in the engineering units of the source channel) to be
assigned to the minimum output (0 or 4 mA) of the selected range.
High limit
None
Allows a value (in the engineering units of the source channel) to be
assigned to the maximum output (20 mA) of the selected range.
Table A15.0 Retransmission option configuration parameters
Select source
for specified
o/p
Select
retransmission
o/p for config.
Select output
type
Main menu item
Enter value for
low limit
Enter value for
high limit