It is compulsory the installation of a windproof roof in accordance with the regulations . The T
inspection, placed at the base, can also be placed inside the house ( better if external).
NB:
This system always guarantees the fumes evacuation, also in case of non-electric tension
Connection with multiple junctions
Link that is only done in cases of particular disadvantages in rankings. In this case the horizontal
section must have a minimum slope of 3% upwards and must not exceed 3 meters, the vertical
section that goes from the stove to the second curve must be at least 1.5 meters long. The T
inspection, at the base, can also be applied inside the house (preferably external). If there is a
fireplace, it must have a preferably circular internal section; the square or rectangular sections must
have rounded corners with a radius of at least 20mm, rectangular sections, with a maximum ratio of
1.5 between the sides, they must have a constant internal section, free and independent; at the
base there must be an inspection hole. Always make a minimum draught of 10Pa and comply with
the UNI 10683.
NB: In case of obstruction of the pipe, due to failures, or bird's nest, the stove will go on the block
(see the Alarms section) and it will be necessary to clean or repair the pipe, and ventilate the
environment as quickly as possible, otherwise, it will saturate with smoke.
NOTE: The cleaning of the pipe should be done annually.