eta PelletsCompact Series Operation Download Page 8

8

www.eta.co.at

Subject to change due to technical improvements

Chimney  

Chimney renovation before it's too late

Compared to older boilers, modern ones are much 
more efficient and have lower amounts of flue gas 
with considerably lower temperatures.

Flues with "too large a cross-section" (over 18 cm) 
in particular are no longer heated adequately. The 
moisture contained in the exhaust gases condenses 
in the flue and in this way leads to very slow but 
inexorable destruction of old masonry chimneys.

Furthermore, if the diameter of the flue is too large, 
the exit velocity and temperature are too low. The 
flue gas then lacks the energy to rise and in extreme 
cases, the smoke can sink down along the roof.

If your flue does not have a moisture-resistant 
lining or its diameter is too large, it will need to be 
renovated with the addition of a moisture-resistant 
inner lining. Narrow flues can also be renovated 
with stainless steel pipes. 

Also keep in mind that chimneys have a limited 
service life. Timely renovation before the chimney 
wall has been destroyed can be performed quickly 
and easily by inserting a tube. But if the flue gas 
condensates have penetrated the mortar joints, then 
the entire flue must be dismantled and rebuilt.

Sealed connection pipe to chimney

A sealed flue pipe is an absolute necessity. Joints can 
be sealed with heat-resistant silicone (300 °C) and/
or pure aluminium tape to prevent the escape of 
dust or flue gas. 

Technical requirements for the flue

can be found in the installation instructions  
(a separate document from this user manual).

Chimney

 

Summary of Contents for PelletsCompact Series

Page 1: ...Operation PC 20 to 32 kW Software 1 20 0 2011 12 PelletsCompact 20 to 32 kW Operation 2012 01 30 EN...

Page 2: ...Changing the fill up time 33 Filling up the storage tank 33 Adjusting the ash removal idletime 34 Changing the deashing interval 35 Meanings of symbols Important NOTICES for operation CAUTION Failure...

Page 3: ...em configuration set by the heating system expert Only your technician or a customer service employee should change settings at the SERVICE level Before making any adjustments to these settings yourse...

Page 4: ...aning agents to prevent corrosion of the boiler and chimney Water is the intended heat transfer medium For special anti frost requirements up to 30 glycol may be added Softened water is required for t...

Page 5: ...ience without having the installation checked by a trained and responsible expert we exclude defects in our delivery and consequential damages resulting from this cause from our warranty guarantee and...

Page 6: ...ide CO emissions of every boiler to be measured periodically In Germany this periodical measurement must also include a dust measurement There are several aspects of this that could go wrong resulting...

Page 7: ...proven solution for passive houses A recirculation cooker hood needs no air supply In passive houses with controlled ventilation in the living quarters this is the preferred solution to keep the vent...

Page 8: ...down along the roof If your flue does not have a moisture resistant lining or its diameter is too large it will need to be renovated with the addition of a moisture resistant inner lining Narrow flue...

Page 9: ...The pellet bin 2 has a capacity of 60 kg Suction takes place once a day at a time that can be set as needed Only on very cold days might it be necessary for pellets to be transported to the boiler a s...

Page 10: ...bin X Expert Lubricate drive chains for stoker cleaner and grate X Expert Inspect ash box position switch and seals X Expert Check strainer in pellet bin X Expert Measuring orifice and hoses on differ...

Page 11: ...g message Water pressure too low For Water pressure too low warning at 1 5 bar and shutdown at 1 0 bar fill the cold heating system to approx 1 8 bar and the hot heating system to approx 2 2 bar Confi...

Page 12: ...ash box can be removed Push up the front panel The front panel stays in place in every position Ash box Open the side latches Open the side latches by pressing the safety catch in the direction of the...

Page 13: ...ger appear The filling level must then be checked manually at regular intervals Boiler TUE 4 4 2011 11 25 45 Reminder check ash box Counter reset when ash box removed Empty out ash check water pressur...

Page 14: ...message and then begin with the maintenance Empty the ash box check the boiler pressure Empty the ash box and check the boiler pressure See page 11 and page 12 Stop heating let boiler cool for at lea...

Page 15: ...sh box to remove the combustion chamber cover from the combustion chamber and scrape the ash from the walls Sweep the ash into the combustion chamber and the tubular heat exchanger Combustion chamber...

Page 16: ...d insert the combustion chamber cover Clean the combustion chamber cover and insert it into the combustion chamber Inspect seal on heat exchanger cover Clean the heat exchanger cover and check the int...

Page 17: ...n available if the valve no longer seals If the valve still cannot be closed tightly after being rinsed several times it must be cleaned or replaced Buffer storage tanks with solar charging must also...

Page 18: ...tension The chain can be tensioned by shifting the motor Lubricate the drive chain for the grate and cleaning drive with spray oil To do so start ash removal by pressing to start the chain moving so t...

Page 19: ...the residual oxygen content of the flue gas and uses this to control the combustion In order to ensure that this works correctly the boiler automatically calibrates the lambda probe at regular interva...

Page 20: ...ched off detach both hoses from the differential pressure transmitter Using the Service access level tap the Inputs line in the boiler s text menu Select Measuring orifice from the submenu and read th...

Page 21: ...to 32 kW 2011 12 Maintenance Expert maintenance after 10 000 kg Drive chain for stoker Drive chains for cleaner and grate Fill level sensor Hoses for differential pressure transmitter Safety valve Fi...

Page 22: ...the highest point in the distribution network and at the top of the buffer significantly reduce the danger of rust and also the frequency of radiator venting Approval Every heating system must be appr...

Page 23: ...further course of the system s service life To have a sufficient safety reserve for additions the new system must be filled with softened water meaning that the empty system must really be filled exc...

Page 24: ...with low thermal capacity For above average hot water needs or high peak demand a pellet boiler needs up to 20 minutes from standby to maximum output and this must bridged with a buffer For air heatin...

Page 25: ...temperature limiter and thermal emergency cooling valve This emergency cooling is shown on the monitor Emergency cooling The heat dissipation is limited with the maximum flow temperature set in the h...

Page 26: ...the screen The touchscreen only displays those function blocks that are required and configured to work with your heating system You can use the horizontal buttons to flick between the individual func...

Page 27: ...witching to the toolbox Press the button to switch to the toolbox Tapping the button with the flag symbols Tap the button with the flag symbols to go to the language selection screen Selecting a langu...

Page 28: ...anging the names of the function blocks The names of the function blocks can be changed at any time in order to make them clearer to you For example the names of the heating circuits HC HC2 etc can be...

Page 29: ...ause of the error has actually been dealt with Some alarms cannot be confirmed until the error has been successfully resolved The display windows for such alarms can be removed using the Confirm later...

Page 30: ...xt menu for the selected function block appears The individual parameters for the selected function block are displayed Lines preceded by have a submenu which can be opened by tapping the line The sub...

Page 31: ...vents refilling during the night This time applies for every day of the week Boiler pressure 2 10 bar Current boiler pressure The current water pressure in the heating system is displayed The pressure...

Page 32: ...heating The cause can be found in the list of error messages Failure during ash removal The ash screw has been switched off due to excessive current consumption This may be due to the ash box being f...

Page 33: ...ress the button to save the new time The fill up time has now been changed The new time applies for every day of the week Fill up pellets function The Fill up pellets function can be used to fill up t...

Page 34: ...d in the submenu tap the Ash removal line Double tap the Start idletime line 2x A settings screen opens Enter the new time and press to save changes Press the button to return to the overview Adjustin...

Page 35: ...ter consultation with an expert or ETA Customer Service Deashing interval factory settings PU 7 11 PU 15 PC 20 32 At earliest after 15 kg 18 kg 30 kg At latest after 25 kg 30 kg 50 kg Changing the Ear...

Page 36: ...sor Timer The timer shows the set heating time slots for the current day of the week Tapping this timer brings up a screen where it is possible to set 3 time slots for each day of the week If a room s...

Page 37: ...cken von Gehen in einer Heiz Pause berspringt das n chste Heiz Zeitfenster Outdoor 13 C Current outside temperature The current outside temperature is measured by the built in outside temperature sens...

Page 38: ...pating excess heat Also displayed during emission measurement On Overtemperature The heating circuit is in operation because the boiler is running at overtemperature The heating circuit is running at...

Page 39: ...eating circuit is within a time slot but switched off The current room temperature is higher than the set Room target temperature by at least the RoomOffDiff temperature Off Hot water The heating circ...

Page 40: ...s in Night mode If a room sensor is installed this regulates the heating circuit to the stored set back temperature for the time slot If there is no room sensor the flow temperature of the heating cir...

Page 41: ...ting only ever applies for the selected heating circuit The hot water supply from the hot water tank or the fresh water module is not affected by the Holiday function For Holiday mode the heating circ...

Page 42: ...iators with metal pipes can take temperatures up to 85 C Heating curve Day During a set time slot the heating circuit is in Day mode The heating curve for Day mode can be adjusted using the parameters...

Page 43: ...he new heating threshold for Day mode Press to save the new value Press to open the Heating circuit overview The parameter Night Heating threshold If the heating circuit is in Night mode an outside te...

Page 44: ...ced or increased 0 30 20 10 Heating flow temperature C 20 10 15 80 70 60 50 40 10 5 0 5 20 15 Outside temperature C Transition period set point Day Night Do not change the flow temperature Flow at 10...

Page 45: ...temperature for this heating circuit Press to save the new value The text menu for the selected heating circuit is displayed Press to open the Heating circuit overview Adjusting the heating curve for...

Page 46: ...y by setting the enable temperature lower than that for all the other heating circuits in the system Opening the heating circuit text menu Press to open the text menu for the selected heating circuit...

Page 47: ...The control system subtracts the Set back parameter from the heating curve Day to get the heating curve Night Outside the time slots set in the timer the heating circuit is in Night mode and runs usi...

Page 48: ...ALARM present Adjusting the room sensor Open the cover by pressing in the latch 4 and turn the control knob 2 to the middle position The measured room temperature can be adjusted using potentiometer P...

Page 49: ...by 15 Enter stock This button can be used to enter the new stock quantity after a delivery of pellets 3758 kg in pellet store Stock The calculated stock of the pellet store is displayed here It is no...

Page 50: ...rew is switched off and the boiler aspirator keeps running for the Aspirator shut off period in order to rinse the hoses Aspirator delay M The maximum fill up time has been exceeded the aspirator will...

Page 51: ...ation by 15 Operating state Current stock may differ from actual stock by 15 Entering stock quantity Manually switching between suction heads Switching unit Green line between switching unit and sucti...

Page 52: ...ted conveying of pellets it was not possible to fill the storage tank The pellet store may be empty or the hoses may be damaged Reference The switching unit is moving to its reference point Stop Filli...

Page 53: ...following icons are displayed in the overview Switching unit switching suction head Once the maximum fill up level parameter Switching at has been reached the switching unit automatically switches to...

Page 54: ...ton A screen opens Enter the new stock quantity and press to save The display returns to the overview The Switching at parameter This parameter is used to define how often pellets are conveyed from a...

Page 55: ...f the Internet connection is indicated by an icon at the bottom of the screen The data is transmitted via the Internet adding to the amount of data you download via your connection In order to avoid e...

Page 56: ...the bottom of the screen The remote control system has 3 different operating modes A different operating mode can be selected for each touch screen Remote control must always be set to Off or Only Vie...

Page 57: ...rs functions If a blocked command is selected while remote control is active a notice window will appear If no buttons are pressed this notice window automatically disappears after 4 seconds If the On...

Page 58: ...w meinETA at Any errors or warnings that are displayed can and may only be rectified on site i e directly via the boiler Rectifying an error using the remote control is not permitted This is because d...

Page 59: ...ortant for reducing the download volume for Internet connections without a flatrate tariff The touch screen remains connected to the meinETA server via the Internet Automatic logout after 10 minutes o...

Page 60: ...assword For the login at www meinETA at it is only possible to change the password Your username will always stay the same even if you change the e mail address in your personal details If you change...

Page 61: ...s See your user manual for information about these In this way you can ensure that your heating system and its safety features will work effectively to provide efficient and low emission operation You...

Page 62: ...ce cleaning Work performed parts replaced Keep records for service maintenance or repairs We recommend that you keep records about all service and maintenance work as well as malfunctions These record...

Page 63: ...63 Operation PC 20 to 32 kW 2011 12 Service and maintenance records Date Performed by Service maintenance cleaning Work performed parts replaced...

Page 64: ...prior to entering storeage area Ensure that the ETA pellet boiler is in automatic mode while store is being filled Switch main power supply to OFF before entering the pellet storage area Smoking nake...

Reviews: