56
www.eta.co.at
Subject to change due to technical improvements
Changing the operating mode
Remote Control
Changing the operating mode of the remote
control system
In the "Boiler" overview, tap the remote control
icon at the bottom of the screen.
A selection window appears:
Tap the operating mode you require to select it.
Switch remote control back on
If remote control has been switched off, it can only
be switched on again via the touch screen of the
boiler or the control system.
To re-activate remote control, tap the
icon on the touch screen and select "On"
in the window that appears.
The
symbol appears while the
connection is being established.
Changing the operating mode
Remote control operating modes
In the boiler overview, the current remote control
mode is shown at the bottom of the screen. The
remote control system has 3 different operating
modes.
A different operating mode can be selected for each
touch screen.
Remote control must
always be set to
"Off" or
"Only View"
before rectifying errors or performing
maintenance work.
"On"
Remote control is on and the unit is connected to
the Internet. The heating system can be controlled
remotely.
"Off"
Remote control is switched off. The remote control
can only be switched on again directly via the
touch screen of the boiler or the control system.
"Only View"
In "Only View" mode, the touch screen is displayed
via the homepage <www.meinETA.at>. The
boiler can be
monitored
, but it is
not possible
to send
commands via remote control.
Remote control must
always be set to
"Off"
or "Only View" before rectifying errors
or performing maintenance work
. This
prevents others from switching the boiler on via
remote control while an error is being fi xed or
maintenance is being carried out.
Changing the operating mode