3. From the Select Module dialog box expand Communications and select “Generic Ethernet-
Module”. Press “OK”.
4. On the New Module Properties Page (General tab):
a.
Assign a unique Name (such as EzMD)
b.
Assign the Metal Detector IP Address (such as 10.10.10.10). Please note that this
must match the address set on the PLC Configuration page of the metal detector.
c.
Set Assembly Instance Input to 101 and Size to 6.
d.
Set Assembly Instance Output to 110 and Size to 6.
e.
Set Assembly Instance Configuration to 148 and Size to 0.