SmartEdge 600 Router Hardware Guide
Table 2
DC Electrical Specifications
Requirement
Value
Total input power, maximum
2736 VA
Input current rating per feed
57 ADC@–48 VDC
Source DC power requirement
Sufficient to supply the rated input current Local codes apply
Number of input feeds
Two: One from battery plant A and one from battery plant B
Table 3
AC (Optional) Electrical Specifications
Requirement
Value
Input voltage, nominal
200 to 240 VAC
Input voltage range
175 VAC to 275 VAC
Input power, maximum
3120 VA
Input current rating
15.6A maximum @ 200 to 240 VAC
Input line frequency, nominal
50 to 60 Hz
Input line frequency, range
47 to 63 Hz
Source AC power requirement
20A, IEC-320
Number of input feeds
Two independent branch circuits
Table 4
Operating and Inrush Current for Line Cards at –48 VDC
Component
Operating Current
Inrush Current
(1)
ATM OC-3c/STM-1c (8-port)
ATM OC-3c/STM-1c (4-port)
Enhanced ATM OC-12c/STM-4c IR (1-port)
2.98
1.88
1.80
0.55
4.96
4.98
2