ENFORCER
Heavy-Duty Outdoor Access Control Keypad with Proximity Reader
32
SECO-LARM U.S.A., Inc.
Programming the Egress Delay/Warning/Alarm (Continued):
When programming the egress delay/warning/alarm, use this general formula:
– Program Egress Delay/Warning/Alarm
– Egress Mode
– Delay Time
Egress Modes:
There are six possible egress operation configurations for the keypad:
•
– Momentary contact
with no warning (default) – Press the egress button momentarily for
silent egress operation.
•
–
Momentary contact with warning beep – Press the egress button momentarily. The keypad
will beep for the programmed delay time before letting the door open, to warn that someone is
preparing to exit the protected area.
•
– Momentary contact with warning beep and alarm – Press the egress
button momentarily.
The keypad will beep and activate the alarm output for the programmed delay time before letting
the door open, to warn that someone is preparing to exit the protected area.
•
–
Hold contact with no warning – Press and hold the egress button for the programmed delay
time until the door is open. This prevents accidental opening of the door.
•
–
Hold contact with warning beep – Press and hold the egress button for the programmed
delay time until the door is open. The keypad will beep during the delay time before letting the
door open, to warn that someone is preparing to exit the protected area.
•
–
Hold contact with warning beep and alarm – Press and hold the egress button for the
programmed delay time until the door is open. The keypad will beep and activate the alarm
output during the delay time before letting the door open, to warn that someone is preparing to
exit the protected area.
NOTE:
When an egress button is programmed to hold for a delay time before the door is released,
it is important to put a sign near the egress button to notify users of the delay time.
Delay Time:
•
– No delay time
(default): Output #1 operates immediately when the egress button is
pressed.
•
to
– Egress button delay time: The delay time can be set from 1 to 99 seconds. This
tells the keypad how long to wait after the egress button is pressed before activating output #1.