Programming the Door-Propped-Open Warning and Delay Time:
Programming the Door-Forced-Open Warning and Timing:
If the keypad is connected to an optional magnetic contact or other door protection switch or
device, the keypad can be programmed to beep when a door has been propped open. This
prompts authorized users to close a door that was not closed properly or to investigate a door that
may have been deliberately propped open.
To Program:
•
Door-propped-open warning OFF (default):
•
Door-propped-open warning ON:
If the keypad is connected to an optional magnetic contact or other door protection switch or
device, the keypad can be programmed to beep and output to an alarm when a door has been
forced open. The keypad beep and alarm output can be set to activate for 1 to 999 seconds.
To Program:
•
Door-forced-open warning OFF (default):
•
Door-propped-open warning ON:
NOTES:
•
represents the beep active and alarm output time, which can be set from 1 to 999
seconds.
•
If programmed for door-forced-open warning, the keypad will beep and the alarm will output if
the door is forced open without using a user code and/or card or the egress button. The keypad
will not beep if the door is opened with a user code and/or card or the egress button.
•
The door open alarm and door-forced-open warning should not both be enabled, as the overlap
in timing could result in incorrect alarm output (see "Programming the Door Open Alarm and
Timing," pg. 31).
•
The "K or A" jumper must be set to "A" for the alarm output to function correctly (see the
"Jumper Settings" table, pg. 9).