SOLARDRIVE
PLUS
PROGRAMMING
GUIDE
60
/
107
2.6.4.4. List of parameters C008 to C042
Parameter
Function
User Level
Default Value
MODBUS
Address
C008
Rated Mains Voltage
BASIC
2:[380
480V]
1008
C010
Type ff Control Algorithm
NOT
ADJUSTABLE
0: IFD
1010
C011
Type ff Reference
NOT
ADJUSTABLE
0: Speed (MASTER mode)
1011
C012
Speed Feedback from Encoder
NOT
ADJUSTABLE
0: Speed (MASTER mode)
1012
C013
Type of V/F Curve
BASIC
Depending on size
1013
C014
Phase Rotation
ENGINEERING
0: No
1014
C015
Rated Motor Frequency
BASIC
50.0 Hz
1015
C016
Rated Motor Rpm
BASIC
1420 rpm
1016
C017
Rated Motor Power
BASIC
Depending on size
1017
C018
Rated Motor Current
BASIC
Depending on size
1018
C019
Rated Motor Voltage
BASIC
400.0 V
1019
C020
Motor No-Load Power
ADVANCED
0.0%
1020
C021
Motor No-Load Current
ADVANCED
0%
1021
C022
Motor Stator Resistance
ENGINEERING
Depending on size
1022
C023
Leakage Inductance
ENGINEERING
Depending on size
1023
C024
Mutual Inductance
ADVANCED
250.00mH
1024
C026
Time Constant Of Bus Voltage
Low-Pass Filter
ENGINEERING
0 ms
1026
C028
Min. Motor Speed
BASIC
0 rpm
1028
C029
Max. Motor Speed
BASIC
1500 rpm
1029
C031
Max. Speed Alarm
ADVANCED
0: Disabled
1031
C032
Reduction in Quadratic Torque
Curve
ADVANCED
30%
1032
C033
Rated Revs Referring to Reduction
in Quadratic Torque Curve
ADVANCED
20%
1033
C034
Voltage Preboost for IFD
BASIC
Depending on size
1034
C035
Voltage Boost 0 at Programmable
Frequency
ADVANCED
Depending on size
1035
C035a
Frequency for Boost 0 Application
ADVANCED
5%
1052
C036
Voltage Boost 1 at Programmable
Frequency
ADVANCED
Depending on size
1036
C037
Frequency for Application of
Voltage Boost 1
ADVANCED
Depending on size
1037
C038
Autoboost
ADVANCED
Depending on size
1038
C039
Slip Compensation
ADVANCED
0: Disabled
1039
C040
Voltage Drop at Rated Current
ADVANCED
0: Disabled
1040
C042
Vout Saturation Percentage
ENGINEERING
100%
1042