SOLARDRIVE
PLUS
PROGRAMMING
GUIDE
54
/
107
P712
Dry-Run Trip Time
Range
0 ÷ 32000
0 ÷ 3200.0 s
Default
200
20.0 s
Level
ADVANCED
Address
894
Function
Minimum time for the Dry-run condition to be true before triggering the function activation as per
P716
.
P713
Dry-Run Autoreset Time
Range
0 ÷ 3200
0 ÷ 3200 s
Default
30
30 s
Level
ADVANCED
Address
895
Function
Timeout for condition reset from the latest Dry-run detection event.
If
P716
is set as Alarm or Warning, this value is the start point of the reset countdown.
P714
Filter Time Constant for Detection Quantity
Range
0 ÷ 32000
0 ÷ 32000 ms
Default
300
300 ms
Level
ADVANCED
Address
896
Function
First order filter time constant applied to the reference variable chosen in
P710.
Useful in case of electric noise affecting the variable.
P715
MDI for Dry-Run Disable
Range
0 ÷ 24
0 ÷ 24:XMDI8
Default
0
0: Disable
Level
ADVANCED
Address
897
Function
If a digital input is set, when the signal is high, the Dry-run detection is disabled.
P716
Dry-Run Action Selector
Range
0 ÷ 3
0: Disable
1: Alarm
2: Warning
3: Only MDO
Default
0
0: Disable
Level
ADVANCED
Address
898
Function
When a Dry-run condition is detected for a time equal to at least the time set in
P712
, the selected
action is executed.
The default setting is “No action”. The possible options are the triggering of an alarm (inverter stop) or
a warning signal (displayed on the keypad, but the inverter is kept running).
If an MDO for Dry-run detection is allocated to this function from the
Digital Outputs Menu
, its status
will be changed in cases 1, 2 and 3.
Option 3 is required to have only the
MDO
command without any additional signal.