SOLARDRIVE
PLUS
PROGRAMMING
GUIDE
64
/
107
C024
Mutual Inductance
Range
0
65000
0.00
650.00mH
Default
25000
250.00mH
Level
ADVANCED
Address
1024
Function
This parameter defines the mutual inductance of the connected motor.
The approximate value of the mutual inductance results from no-load current according to the formula
below:
M
(Vmot
– Rstat*Io) / (2
fmot* Io)
C026
Time Constant of Bus Voltage Low-pass Filter
Range
0
32000
0.0
3200.0 ms
Default
0
0.0 ms
Level
ENGINEERING
Address
1026
Function
This parameter defines the time constant of the low-pass filter of the bus voltage readout.
Changing this value can avoid motor oscillations, especially when no load is connected to the motor.
C028
Min. Motor Speed
Range
–32000
32000 (*)
–32000
32000 rpm (*)
Default
0
0 rpm
Level
BASIC
Address
1028
Function
This parameter defines the minimum speed of the connected motor. This is the reference speed
forced when the active speed reference is at its minimum value.
NOTE
The value set as the min. speed is used as the saturation of the global reference; the speed
reference will never be lower than the value set as min. speed.
C029
Max. motor speed
Range
0
32000 (*see note in
parameter
C028
)
0
32000 rpm (*see note in parameter
C028
)
Default
1500
1500 rpm
Level
BASIC
Address
1029
Function
This parameter defines the maximum speed of the connected motor.
This is the reference speed forced when the active speed reference is at its maximum value.
NOTE
According to factory setting, when the equipment is AC power supplied (from optional, auxiliary
AC grid), the motor speed reference is equal to the value in parameter C029.