PROGRAMMING
GUIDE
SOLARDRIVE
PLUS
93
/
107
A039
Texas Flash not Programmed
Description
Texas Flash not programmed
Event
When switched on, DSP Motorola detected that Flash Texas is not correctly programmed.
Possible cause
A prior attempt to download DSP Texas software failed.
Solution
1. Download the correct DSP Texas software version.
2. If the alarm persists, please contact ENERTRONICA SANTERNO
’s Customer Service.
A040
User Alarm
Description
Alarm trip caused by the user (as a testing procedure)
Event
The user has forced the alarm to trip.
Possible cause
Value 1 was entered to address MODBUS 1400 via serial link.
Solution
Reset the alarm: send a
RESET
command.
A041
IGBT Fault Side A
Description
General hardware fault from IGBT, side A
Event
Power converter A generated a general alarm.
Possible cause
•
Electromagnetic disturbance or radiated interference.
•
Overcurrent, IGBT overtemperature, IGBT fault.
Solution
1. Reset the alarm: send a
RESET
command.
2. If the alarm persists, please contact ENERTRONICA SANTERNO
’s Customer Service.
A042
Illegal XMDI in DGI
Description
Illegal configuration of XMDI in the Digital Inputs Menu.
Event
The drive has detected a parameter configuration error.
Possible cause
Wrong settings.
Solution
Check settings and enter correct settings.
Contact ENERTRONICA SANTERNO
’s Customer Service.