SOLARDRIVE
PLUS
PROGRAMMING
GUIDE
30
/
107
2.4.2.
First Start Up
The Solardrive Plus accepts the IFD control mode only (
C010
).
1) Wiring:
Follow the instructions stated in Solardrive Plus
2) Power on:
Power on the drive with the emergency button pressed to prevent the motor from
running. Check if the display/keypad turns on.
3) Parameter
setting:
The equipment startup is made easier by the Start Up Menu (section 2.4), which is a
wizard for the set up of the main motor control parameters.
From the Start Up Menu, set the motor ratings:
•
C015
(fmot1)
Rated motor frequency
•
C016
(rpmnom1)
Rated motor rpm
•
C017
(Pmot1)
Rated power
•
C018
(Imot1)
Rated current
•
C019
(Vmot1)
Rated voltage
•
C029
(Speedmax1)
Max. allowable speed.
Enter the main parameter for pumping applications:
•
C800
(SpeedMinPump)
Minimum Pump Speed:
When the pump speed drops below the threshold in
C800
, the pump is
stopped. See 2.6.9.
•
P009
(Tup1)
Acceleration Time at Start 1:
Acceleration ramp, expressed in seconds for the system to go from
0 rpm to the maximum allowable speed set in
C029
. See section 2.6.9.
•
P010
(Tdn1)
Deceleration Time at Stop 1:
Deceleration ramp, expressed in seconds for the system to go to the
maximum allowable speed set in
C029
to 0 rpm. See section 2.6.1.
•
P018
(Tacc_in)
Acceleration Start Time:
Ramp applied during the initial stage of the ramp, from the motor startup
to the instant when the frequency set in parameter
P020
is attained. See
section 2.6.1.
•
P019
(Tdec_fin)
End Deceleration Time:
Ramp applied during the final stage of the ramp, starting from the speed
value set in
C020
. See section 2.6.1.
•
P020
(Spd_IFramps)
Speed Threshold for Initial and Final Ramps:
Threshold used for ramps
P018
and
P019
. See section 2.6.1.
•
C265
(ThermProt M1)
Motor Thermal Protection Enable and Type of
Derating for
M1:
Motor thermal protection configuration. See section 2.6.8.
•
C267
(ThermConstM1)
Thermal Time Constant for motor M1
.
See section
The motor V/f pattern may be programmed in
C013
. For loads with quadratic torque in
respect to the rpm (centrifugal pumps, fans, etc.), set
C034
(preboost1) to 0%.
4) Overload:
Set parameters
C043
,
C044
and
C045
as the maximum desired overload current.
5) Startup:
Press the
LOC/REM
key on the Display/keypad: the L-CMD LED and L-REF LED
come on and the drive will enter the local mode. Set the speed reference by pressing