PROGRAMMING
GUIDE
SOLARDRIVE
PLUS
61
/
107
C008
Rated Mains Voltage
Range
0
8
0: [ 200
240 ] V
1: 2T Regen.
2: [ 380
480 ] V
3: [ 481
500 ] V
4: 4T Regen.
5: [ 500
600 ] V
6: 5T Regen.
7: [ 600
690 ] V
8: 6T Regen.
Default
2
2: [ 380
480 ] V
Level
BASIC
Address
1008
Function
This parameter defines the rated voltage of the mains powering the drive, thus allowing obtaining
voltage ranges to be used for the drive operation. The value set in this parameter depends on the
Drive voltage class.
To supply the drive via a non-stabilized DC source, the corresponding AC voltage range must be
used (see Table 10). DO NOT USE xT Regen settings in this case.
Table 10: Equivalence between AC mains range and DC range
AC MAINS
DC range
200
240 Vac 280
338 Vdc
380
480 Vac 530
678 Vdc
481
500 Vac 680
705 Vdc
500
600 Vac 705
810 Vdc
600
690 Vac 810
970 Vdc
C013
Type of V/F Pattern
Range
0
2
0: Constant Torque
1: Quadratic
2: Free Setting
Default
Depending on the size
Level
BASIC
Address
1013
Function
Allows selecting different types of V/f pattern.
If
C013 = Constant torque
, voltage at zero frequency can be selected (Preboost
C034
).
If
C013 = Quadratic
, you can select voltage at zero frequency (preboost,
C034
), max. voltage drop
with respect to the theoretical V/f pattern,
C032
, and the frequency allowing implementing max.
voltage drop,
C033
.
If
C013 = Free Setting
, you can set voltage at zero frequency (preboost,
C034
); voltage increase to
20% of the rated frequency (Boost0,
C035
); and voltage increase to a programmed frequency
(Boost1,
C036
; frequency for Boost1,
C037
).
C014
Phase Rotation
Range
0
1
0: [No]; 1: [Yes]
Default
0
0: [No]
Level
ENGINEERING
Address
1014
Function
Allows reversing the mechanical rotation of the connected motor.