Handbuch-KnxSmartmeter-85A-en-3.odt, 2018-10-04
Seite 67 von 69
ID
Name
Object function
Length
Type
Flags
146 Intermediate
counter 6
Cost counter-current value
4 Byte
[13.001]
DPT_Value_4_Cou
nt
CR-T-
This object contains the current cost counter value of the intermediate counter in ct. The counter value may be
positive or negative. The value of the group object is respectively copied after the lapse of the counting interval into
the group object “Cost counter - previous value” and then reset.
ID
Name
Object function
Length
Type
Flags
147 Intermediate
counter 6
Cost counter-previous value.
4 Byte
[[13.001]
DPT_Value_4_Cou
nt
CR-T-
The object contains the cost counter value from the previous count interval of the intermediate counter in ct. If
configured, this value is transmitted on the bus after its update. When transmitting the parameter “General - Offset
when transmitting of intermediate counter values in (s)” operates as a transmission delay.
ID
Name
Object function
Length
Type
Flags
148 Intermediate
counter 6
Limit message
1-Bit
[1.002]
DPT_Bool
C--T-
Group object that transmits the value 1 or 0, if the limit of the intermediate counter has been exceeded or fallen
below.
ID
Name
Object function
Length
Type
Flags
149 Intermediate
counter 6
External energy counter limit
4 Byte
[13.010]
DPT_ActiveEnergy
CR-T-
When writing to this object the limit is adopted from the bus. If the parameter “Adopt limit value from the bus” is set on
“flighty” then the value adopted by the bus is discarded after the next reset of the intermediate counter. If in contrast
the parameter is set on “permanent” then the limit adopted by the bus is permanent.
ID
Name
Object function
Length
Type
Flags
150 Intermediate
counter 6
External cost counter limit
4 Byte
[13.001]
DPT_Value_4_Cou
nt
CR-T-
When writing to this object the limit is adopted from the bus. If the parameter “Adopt limit value from the bus” is set on
“flighty” then the value adopted by the bus is discarded after the next reset of the intermediate counter. If in contrast
the parameter is set on “permanent” then the limit adopted by the bus is permanent.
ID
Name
Object function
Length
Type
Flags
151 Intermediate
counter 6
Reset counter value
1-Bit
[1.017]
DPT_Trigger
C-W--
If the value 1 is transmitted to this object, then the intermediate counter behaves as it reaches a time interval
boundary. The group object is released by the parameter selection “Count interval - by trigger object”. See also
section Intermediate Counter.
ID
Name
Object function
Length
Type
Flags
152 Tariff
Tariff changeover
1 Byte
[5.006]
DPT_Tariff
CRWT-
With this object it can be specified, which tariff is currently valid. Acceptable values are “0” = no tariff, “1” = tariff 1, “2”
= tariff 2 and “3” = tariff 3. If a tariff is activated, the other two tariffs are terminated. When reading this object the
current-active tariff is issued. See also section Tariff Costs Counter
ID
Name
Object function
Length
Type
Flags
153 Tariff 1
Trigger (Tariff start)
1-Bit
[1.017]
DPT_Trigger
C-W--
If the parameter “By trigger objects” in “Tariff switch tariff 1” is set, then tariff 1 is started when receiving this object.
The value of the object is not taken into account.
ID
Name
Object function
Length
Type
Flags
154 Tariff 1
Trigger (Tariff stop)
1-Bit
[1.017]
DPT_Trigger
C-W--
If the parameter “By trigger objects” in “Tariff switch tariff 1” is set, then tariff 1 is stopped when receiving this object.
The value of the object is not taken into account.
Enertex
®