Handbuch-KnxSmartmeter-85A-en-3.odt, 2018-10-04
Seite 56 von 69
ID
Name
Object function
Length
Type
Flags
49
Measurement
Ch3
Active power limit message
1 Bit
[1.002]
DPT_Bool
C--T-
Group object, that is transmitted with the value 1 or 0, if the limit of the active power of channel 3 has been exceeded
or fallen below.
ID
Name
Object function
Length
Type
Flags
50
Measurement
Ch3
Voltage limit message
1 Bit
[1.002]
DPT_Bool
C--T-
Group object, that is transmitted with the value 1 or 0, if the limit of the voltage of channel 3 has been exceeded or
fallen below.
ID
Name
Object function
Length
Type
Flags
51
Measurement
Ch3
Voltage failure message
1 Bit
[1.002]
DPT_Bool
C--T-
Group object, that is transmitted with the value 1 or 0, if the voltage at channel 3 exceeds or falls below 60Vrms.
ID
Name
Object function
Length
Type
Flags
52
Measurement
Ch3
Voltage peak message
1 Bit
[1.002]
DPT_Bool
C--T-
Group object that transmits the value 1 if at channel 3 a transient voltage spike greater than 650V is detected.
ID
Name
Object function
Length
Type
Flags
53
Measurement
Ch3
Current limit message
1 Bit
[1.002]
DPT_Bool
C--T-
Group object, that is transmitted with the value 1 or 0, if the limit of the current of channel 3 has been exceeded or
fallen below.
ID
Name
Object function
Length
Type
Flags
54
Measurement
Ch3
Current peak message
1 Bit
[1.002]
DPT_Bool
C--T-
Group object that transmits the value 1 if at channel 3 a transient current spike greater than 140A is detected.
ID
Name
Object function
Length
Type
Flags
55
Measurement
Ch3
THD-U limit message
1 Bit
[1.002]
DPT_Bool
C--T-
Group object, that is transmitted with the value 1 or 0, if the limit of the THD-U of channel 3 has been exceeded or
fallen below.
ID
Name
Object function
Length
Type
Flags
56
Measurement
Ch3
THD-I limit message
1 Bit
[1.002]
DPT_Bool
C--T-
Group object, that is transmitted with the value 1 or 0, if the limit of the THD-I of channel 3 has been exceeded or
fallen below.
ID
Name
Object function
Length
Type
Flags
57
Measurement
Ch3
Apparent power
4 Byte
[14.056]
DPT_Value_Power
CR-T-
Group object with the most recently determined apparent power of the channel 3.
ID
Name
Object function
Length
Type
Flags
58
Measurement
Ch3
Reactive power
4 Byte
[14.056]
DPT_Value_Power
CR-T-
Group object with the most recently determined reactive power of the channel 3.