56
900-00275-01-001 Rev A ©2021 OutBack Power. All Rights Reserved.
Operation
Bulk Stage
This is the first stage in the cycle. It is a constant-current stage which drives the battery voltage up.
Bulk typically leaves the batteries at 75% to 90% of their capacity, depending on the battery type,
the charger setting, and other conditions.
Displayed
:
Status message:
Bulk
Voltage Used:
Absorb voltage (V)
setting.
Exiting to Absorption stage:
Upon reaching the
Absorb voltage (V)
setting.
The DC current will operate at a high level, often at the charger’s maximum current setting.
The actual charging kilowatts are shown in Figure 28.
To skip this step:
Setting
Absorb voltage (V)
equal to
Float voltage (V)
causes the charger
to proceed through the normal three-stage cycle, but at a single voltage.
Setting
Absorb time (m)
to zero causes the charger to skip both the Bulk
and Absorption stages and proceed directly to the Float stage.
Setting
Absorb charge mode
to
Disable
also causes the charger to skip both
stages and proceed directly to the Float stage.
Figure 28 Absorption Stage
Summary of Contents for OutBack POWER Mojave OGHI8048A
Page 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Page 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Page 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Page 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Page 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...