900-00275-01-001 Rev A
25
User Interface
ACTIONS View
This view displays the
Action Menu
, with various off/on and other commands for basic functions.
It does not replace the
STATUS
,
SETTINGS
, or
EVENTS
views, but appears alongside them.
NOTE:
Clicking on this item a second time, or on the
Action Menu
heading, does not remove it from
the screen. To remove it, press the
×
symbol (see
A
in Figure 9).
Figure 9
User Interface (Action Menu)
B.
Generator
— This drop-down menu has the options
On
,
Off
(start or stop the generator immediately), and
Auto
(enable AGS for automatic generator control; see page 74).
C.
Bulk Charge
— This drop-down menu has the options
Bulk Start
(begin charging) or
Stop
. See either
page 56 or page 66, depending on the battery type. This item may not be required for battery chemistries
other than lead-acid. See page 64.
D.
Inverter
— This drop-down menu has the options
On
(begin inverting; see page 38) or
Off
.
E.
Grid Input
— This onscreen toggle has the options
Use
(connect) or
Drop
(disconnect). This is a
manual command to connect or disconnect from the utility grid.
Use
connects to the grid if all other
conditions are met. (See page 45.)
F.
Gen Input
— This onscreen toggle has the options
Use
(connect) or
Drop
(disconnect). This is a
manual command to connect or disconnect from the generator.
Use
connects to the generator if all other
conditions are met. (See page 72.) It does not influence AGS or any other generator interaction.
NOTES:
If
G r i d
or
G e n
I n p u t
are set to
Use
with
Inverter Off
, the unit will transfer power to loads
(see pages 46 and 73). It will not charge batteries or otherwise interact with the power.
The inverter cannot accept generator power if grid power is already being accepted. (See
page 47.) It can accept the generator if the grid is present but
Grid Input
is set to
Drop
.
G.
Reset Faults
— The
CLEAR
button resets any active errors. When errors appear, they are displayed in
the
Status
field under each of the
STATUS
tabs. See pages 18 through 22.
H.
Apply
— This button finalizes changes to the
Action Menu
. Changes will not take effect otherwise.
A
B
C
D
E
F
G
H
Summary of Contents for OutBack POWER Mojave OGHI8048A
Page 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Page 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Page 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Page 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Page 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...