70
900-00275-01-001 Rev A ©2021 OutBack Power. All Rights Reserved.
Operation
Generator Tab
The items under this tab affect the Mojave inverter’s interactions with an AC generator, particularly
automatic starting.
The items presented here are described on the designated pages. They may not appear in the
same order as shown below.
NOTE
: Although
SYSTEM TIME
on page 15 uses a 24-hour clock format, settable times of day in this menu
are formatted using a 12-hour clock.
Generator output rating (kVA)
— Range:
0
to
100
. Default:
5.0
.
The generator’s size in kilovolt-amps (kVA), usually treated the same as kilowatts (kW). See page 72.
High voltage limit (V)
— Range:
84
to
140
. Default:
130
.
The highest AC voltage the inverter can accept from a generator before disconnection. See page 72.
Low voltage limit (V)
— Range:
85
to
140
. Default:
105
.
The lowest AC voltage the inverter can accept from a generator before disconnection. See page 72.
High frequency limit (Hz)
— Range:
55
to
65
. Default:
63
.
The highest frequency the inverter can accept from a generator before disconnection. See page 72.
Low frequency limit (Hz)
— Range:
55
to
65
. Default:
57
.
The lowest frequency the inverter can accept from a generator before disconnection. See page 72.
Warmup time (s)
— Range:
0
to
1800
. Default:
60
.
The time in seconds the generator is allowed to run with no load (before charging begins). This time
should follow the generator manufacturer’s recommendations. This setting applies only when using AGS.
See pages 72 and 74.
Cooldown time (s)
— Range:
0
to
1800
. Default:
300
.
The time in seconds the generator is allowed to run with no load (after charging has finished). This time
should follow the generator manufacturer’s recommendations. This setting applies only when using AGS.
See pages 72 and 74.
AGS
— Range:
Disabled
or
Enabled
. Default:
Disabled
.
This item controls the Automatic Generator Start (AGS) function. See page 74.
Start on low battery
— Range:
Disabled
or
Enabled
. Default:
Disabled
.
This item allows AGS to start the generator upon reaching a either a low state of battery charge, or
progressively lower battery voltages. See page 76.
Start SoC (%)
— Range:
0
to
80
. Default:
50
.
The low state of charge that causes AGS to start the generator. See page 75.
Stop SoC (%)
— Range:
0
to
100
. Default:
80
.
The high state of charge that causes AGS to stop the generator. See page 75.
24 hour start voltage (V)
— Range:
40
to
64
. Default:
48.8
.
The low battery (DC) voltage that will cause AGS to start the generator after 24 hours. See page 75.
2 hour start voltage (V)
— Range:
40
to
64
. Default:
47.2
.
The low battery (DC) voltage that will cause AGS to start the generator after 2 hours. See page 75.
2 minute start voltage (V)
— Range:
40
to
64
. Default:
44.0
.
The low battery (DC) voltage that will cause AGS to start the generator after 2 minutes. See page 75.
Summary of Contents for OutBack POWER Mojave OGHI8048A
Page 1: ...Mojave Grid Hybrid Inverter Charger OGHI8048A Operator s Manual...
Page 30: ...30 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved User Interface NOTES...
Page 48: ...48 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Operation NOTES...
Page 110: ...110 900 00275 01 001 Rev A 2021 OutBack Power All Rights Reserved Specifications NOTES...
Page 115: ...900 00275 01 001 Rev A 115 Index This page intentionally left blank...