77
017-220-J0 Rev C
• Copy the upgrade firmware file (only .sx or .fbin files NOT .ezip) to a folder on the laptop.
Procedure:
1. On the Alpha Micro 100, put the battery breaker in the OFF position.
2. Turn off the AC input to the Alpha Micro 100.
3. Short the jumper JP1 on the board.
4. Connect the USB cable between the Alpha Micro 100 and the laptop.
5. Put the battery breaker in the ON position.
6. Start the
FXMProgrammer
software.
7. Select a COM port from the drop-down list of available ports.
8. Click
Open File
to browse to the software file location (only .sx or .fbin files are supported).
9. Click the
Apply the update to the FXM unit
button.
10. Watch the progress bar and the
Programming Messages
window. (If there is a connection or any other kind
of error, click
Apply the update again
).
The unit will reset automatically once the upgrade is finished.
11. Close the
FXMProgrammer
software.
12. Put the battery breaker in the OFF position.
13. Remove the jumper on JP1.
14. Put the battery breaker in the ON position.
15. Connect the AC input to the Alpha Micro 100.
Contact Alpha Technologies’ Technical Support at 1-800-667-8743 if you have any questions about this procedure.
Summary of Contents for Alpha Micro 100
Page 1: ...Alpha Micro 100 UPS Technical Guide 017 220 J0 Effective 09 2020...
Page 2: ......
Page 36: ...35 017 220 J0 Rev C Figure 14 Web Interface Bulk Charging Menus...
Page 37: ...017 220 J0 Rev C 36 Figure 15 Web Interface Bulk Charging Menus...
Page 85: ......
Page 86: ......
Page 87: ......