67
017-220-J0 Rev C
9.7.4 Programming the Dry Contacts
The Alpha Micro 100 front panel contacts (C1 and C2) can be programmed to meet your specifications. Each con-
tact can only be programmed for one function at a time and cannot show multiple conditions.
The functions of dry contacts can be changed with HyperTerminal. For example, to change contact C2:
To see how it is currently programmed, type
c2
(all lower case) and press
Enter
.
The Alpha Micro 100 responds with
*c2=2
where the
*
shows the unit responded to your command.
For example: a "
2
" shows it is programmed to be the
Low Battery
indicator.
To change the contact, type
c2=X
where X is 1 to 14 and press
Enter
.
The Alpha Micro 100 responds with
*c2=(1 to 14)
. For example, to change the C2 contact to be the Temperature
indicator, type
c2=11
Table Q — Dry Contact Configuration Settings
1= On Battery
Used for remote indication of the On Battery condition.
2= Low Battery
Used for remote indication of the Low Battery condition.
3= Timer 1
See "Setting the Timer Contact" on page 68.
4= Alarm
Used for remote indication of an Alarm condition.
5= Fault
Used for remote indication of a Fault condition.
6= Disabled
Dry contact is disabled, i.e. never energizes.
7= Timer 2
See "Setting the Timer Contact" on page 68.
8= Timer 3
See "Setting the Timer Contact" on page 68.
9= External Vdc
Not available on Micro 100.
10= Generator
Reserved for future use.
11= Temperature
Not available on Micro 100.
12= Low Battery, Shutdown
Contact will activate when battery is low (factory-defined level) and the unit is running in
Inverter mode. Contact is deactivated when battery level returns to an acceptable value.
13= Low Battery and Line
Used for remote indication that the battery is low in Line mode. This condition can be
used to interpret the health of the battery.
14= LVD (Low Voltage
Disconnect)
The dry contact is energized when the battery voltage is greater than the LVD
CONNECT set voltage (see "Control Parameters" on page 32) and will de-energize if
the battery voltage drops below 21V.
15= Output Relay
The dry contact is used for energizing external output relay. The external AC contactor
can be controlled for disconnect/reconnect by configuring one of the dry contacts as
Output Relay. Output relay option is built-in for Micro 100.
Caution:
On 230Vac models, any relay when configured to “Output relay” is wrongly
triggered during transitions to and from Boost 1 and Boost 2 modes while in AVR
Reduced mode.
Summary of Contents for Alpha Micro 100
Page 1: ...Alpha Micro 100 UPS Technical Guide 017 220 J0 Effective 09 2020...
Page 2: ......
Page 36: ...35 017 220 J0 Rev C Figure 14 Web Interface Bulk Charging Menus...
Page 37: ...017 220 J0 Rev C 36 Figure 15 Web Interface Bulk Charging Menus...
Page 85: ......
Page 86: ......
Page 87: ......