System Display/Programming Modes
The 9312’s Main and System Loops are shown below. These settings apply to those units with Version 3.1 software.
Main Loop
Description
Allowable Range
id
Instantaneous Demand
N/M
Ad
Average Demand
N/M
Pd
Peak Demand
N/M*
dL
On-Peak Demand Limit
2.0-49.5 (4-99 in 80 KW Mode)
CL
Clock - Current Time
12:00 a.m.-11:59 p.m.
System Loop
Description
Allowable Range
dE
Temperature - degrees
N/M
do
Day of the Week
1-7
dA
Date - Month/Day
1/1-12/31
Yr
Year
1992-2090
dS
Auto Daylight-Saving Adjust
0, 1, 2
ns
Number of Seasons
0-4
A1
Winter 1 Start Time
12:00 a.m. - 11:59 p.m.
A2
Winter 1 End Time
12:00 a.m. - 11:59 p.m.
A3
Winter 2 Start Time
12:00 a.m. - 11:59 p.m.
A4
Winter 2 End Time
12:00 a.m. - 11:59 p.m.
Ad
Winter Start Date
0/0-12/31
U1
Spring 1 Start Time
12:00 a.m. - 11:59 p.m.
U2
Spring 1 End Time
12:00 a.m. - 11:59 p.m.
U3
Spring 2 Start Time
12:00 a.m. - 11:59 p.m.
U4
Spring 2 End Time
12:00 a.m. - 11:59 p.m.
Ud
Spring Start Date
0/0-12/31
S1
Summer 1 Start Time
12:00 a.m. - 11:59 p.m.
S2
Summer 1 End Time
12:00 a.m. - 11:59 p.m.
S3
Summer 2 Start Time
12:00 a.m. - 11:59 p.m.
S4
Summer 2 End Time
12:00 a.m. - 11:59 p.m.
Sd
Summer Start Date
0/0-12/31
F1
Fall 1 Start Time
12:00 a.m. - 11:59 p.m.
F2
Fall 1 End Time
12:00 a.m. - 11:59 p.m.
F3
Fall 2 Start Time
12:00 a.m. - 11:59 p.m.
F4
Fall 2 End Time
12:00 a.m. - 11:59 p.m.
Fd
Fall Start Date
0/0-12/31
SS
Saturday/Sunday On/Off-Peak
on/oFF
H1
Holiday 1
0/0-12/31
H2
Holiday 2
0/0-12/31
H3
Holiday 3
0/0-12/31
H4
Holiday 4
0/0-12/31
H5
Holiday 5 (President’s Day)
0/0-12/31, oFFP, onP
H6
Holiday 6 (Memorial Day)
0/0-12/31, oFFP, onP
H7
Holiday 7 (Labor Day)
0/0-12/31, oFFP, onP
H8
Holiday 8 (Thanksgiving Day)
0/0-12/31, oFFP, onP
H9
Holiday 9 (Friday after Thanksgiving)
0/0-12/31, oFFP, onP
oP
Off-Peak Peak Demand
N/M*
oL
Off-Peak Limit
2-49.5, 4-99, oFF, oFF2, oFF3, oFF4, oFF5
HL
High Instantaneous Limit
2-49.5, 4-99, oFF
nr
# of Relays (Loads) Connected
1 to 16
Pr_1
Priority - Load #1
1 to 17
Pr_2
Priority - Load #2
1 to 17
Pr_3
Priority - Load #3
1 to 17
Pr_n
Priority - Load #n
1 to 17
on_1
Minimum On-Time for Load #1
0-20 minutes
on_2
Minimum On-Time for Load #2
0-20 minutes
on_3
Minimum On-Time for Load #3
0-20 minutes
on_n
Minimum On-Time for Load #n
0-20 minutes
oF_1
Minimum Off-Time for Load #1
0-20 minutes
oF_2
Minimum Off-Time for Load #2
0-20 minutes
oF_3
Minimum Off-Time for Load #3
0-20 minutes
oF_n
Minimum Off-Time for Load #n
0-20 minutes
dC
Demand Control Algorithm
1-4
AP
Averaging Period
15, 30 or 60-minutes
dr
Demand Range
40 or 80
*Can reset to 0 but the recorded number is non-modifi able