background image

Display/Settings 
Sequence

     The 9312 contains 2 display sequence loops: the Main 
Loop and the System (or Installation)  Loop. The Main 
Loop contains the following:
 

      

 

        

Instantaneous Demand

 

 

Average Demand

 

 

Peak Demand

 

 

Demand Limit

 

 

Clock

To step through the Main Loop, press the Display Mode 

key (12) to change to next system setting in the loop.

The System Loop contains system information which 

is usually set only when the 9312 is installed. All system 
settings in the System Loop are listed in Appendix B. To 
enter the System Loop from the Main Loop, hold down 
Alarm  Volume key (11)  and  Reset Peak key (13)  simul-
taneously for 5 seconds. If settings are changed, the new 
settings are automatically saved.

Load Control
Strategies & Load
Shedding Sequence

When your total power consumption starts to exceed 

the demand limit setting, the 9312 turns off  (sheds)  the 
lowest priority load which is available. If necessary, 
additional loads will be shed to keep the average demand 
below the demand limit setting. Loads are shed according 
to the load control strategy selected: the fi xed priority strat-
egy, the rotating strategy, a combination, or by the Priority 
17 strategy. See Section 12 in the Installation Manual for 
an explanation on how to select a load control strategy 
described below:

Fixed  Priority  Strategy:

  When this strategy is 

selected, up to sixteen circuits are turned on and off in 
order of priority from 1 through 16, where loads controlled 
by priority level 1 have the highest priority. Loads con-
trolled by priority level 16 are the fi rst off and the last on. 
The on and off decision is made and implemented every 
1-minute. This strategy is useful when low priority loads 
may be turned off without signifi cantly interrupting energy 
use needs. Minimum On and Off-Times may be assigned 
to each circuit. Chart A shows an example of this strategy.

Rotate Strategy:

 For this strategy, all sixteen circuits 

are assigned an equal but rotating priority, which turns off 
loads sequentially every 1-minute as required to maintain 
demand  below the limit. The  fi rst load previously turned 
off is turned on at the beginning of each 1-minute interval. 
This way Off-Time of rotating loads is minimized.

The rotate strategy is particularly useful where equal 

priority rotation may serve several heating loads, minimiz-
ing the Off-Time of each load during rotation. Thus, the 
reduction in demand is shared by several loads and the 

1. Press 

and hold Alarm Volume key (11).

2. Simultaneously 

press the Decrease key (7) or the 

Increase key (8).  The alarm will come on and beep about 
6 times at each volume level.

3.  Release keys at the desired volume.

Note:

  If you desire to turn off the alarm, hold down 

the Alarm Volume key (11) and Decrease key (7) until the 
alarm stops.

Step 7,  If the Alarm Sounds:

  The alarm in your Control/

Display Unit sounds and the Reduce Load Indicator (6) 
will come on when the 9312 has done all it can do to 
reduce your electrical demand, but the actual demand is 
still greater than the demand limit.  That means all circuits 
that your 9312 has control over have been turned off, but 
due to high base load, this is not enough. In this situa-
tion, your demand limit may be unrealistically low for the 
level of comfort or appliance use you desire.  Loads with 
Minimum On-Times may cause the alarm to temporarily 
sound until the particular On-Time has elapsed. 

To silence the alarm, turn off some unnecessary appli-

ances or, if necessary increase the demand limit 0.5 KW at 
a time until the alarm stops.  If you choose to turn off an 
uncontrolled load, you may monitor your actual demand 
in the Instantaneous mode in order to see the effect of each 
load on overall demand (see Table 3). 

Important:

  Only your uncontrolled loads or your 

controlled loads currently under a Minimum On-Time 
can initiate the over-limit alarm. Minimum On-Times are 
described on page 14.

Table 3: Typical Residential Appliance Ratings

 

Stove

 

  Large Burner  

  1.5-2KW

 

  Small Burner  

  1-1.4KW

 

  Oven or Broiler  

  5KW

 

  Self Clean (Bake &

 

  Broil on together)  

  10KW

 

Refrigerator  

  1.5-2KW

 

Dryer  

  4.5-6KW

 

Freezer  

  1.5-2KW

 

Microwave  

1.5KW

 

Water Heater  

  3-6KW

 

Lighting  

  0-1.4KW

 

Dishwasher  

  1.2KW

 

Waffl e Iron  

  1.2KW

 

Toaster  

  1.1KW

 

Hair Dryer  

  2KW

 

Room Air Conditioner  

  0.9KW

 

Vacuum  

  0.7KW

 

Blender  

  0.3KW

 

Mixer  

  0.15KW

 

Television  

  0.12-0.2KW

 

(instant on is 0.3 KW

 

consumption continuously)

 

Central Air Conditioning     3-8KW

 

(depending on home size) 

 

Heat Pump  

  3-25KW

9

id
Ad
Pd
dL
CL

id
Ad
Pd
dL
CL

Summary of Contents for 9312

Page 1: ...Computerized Energy Management Model 9312 Owner s Installation Manual Helping you to use energy more efficiently ...

Page 2: ...ools Materials Required 17 3 0 Pre Installation System Check List 17 4 0 Locating C D Unit 18 5 0 Locating and Mounting Relay Unit 18 6 0 Running Control Cable 19 7 0 Wiring Control Cable to C D Unit 19 8 0 Mounting C D Unit 20 9 0 Wiring Control Cable to Relay Unit 20 10 0 Wiring 120 VAC Power Supply to Relay Unit 21 11 0 Installing Wiring Current Transformers 21 12 0 Creating a Load Schedule Mak...

Page 3: ...FCC Rules which are designed to provide reasonable protection against such interference in a residential installation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interferen...

Page 4: ...de key until the left display reads dL This is your demand limit Simultaneously press the Demand Limit and Increase keys and raise the system s demand limit by 0 5 KW Wait one or two hours to give your home a chance to heat or cool If the change you just made does not feel sufficient after that time press the Demand Limit and Increase key to increase the system s demand limit another 0 5 KW Repeat...

Page 5: ...e is illustrated by the largest spike in Owner A in Figure 1 Under the TOU Demand Rate you pay for both total energy used in Kwh like the Energy Rate and for your peak demand during the On Peak time over the billing period highest average KW demand see page 12 for definition In addition utilities offer reduced or no KW demand charges during the Off Peak times When compared to the Energy Rate the T...

Page 6: ...ower consumption continues to exceed the demand limit it begins to turn off loads It turns off the least impor tant load first using the load control strategy that you set As the power consumption drops it then allows the most important loads to come back on first There are several optional load control strategies A typical strategy might provide power to a higher priority load such as the dryer a...

Page 7: ...ak and Off Peak hours the proportion of energy consumed during On Peak and Off Peak times and the demand limit Superior Features of the 9312 Real Time Control The 9312 contains a real time clock which allows the demand management system to take advantage of TOU Demand Rates available from some utilities and modify the control strategy accordingly This feature enhances the money savings and comfort...

Page 8: ...components the Control Display Unit Relay Unit s and the Current Transform ers The System Diagram in Figure 3 in the Installation Manual shows how these components are connected to control loads at the circuit breaker panel Your 9312 con trols only those loads which are connected to it However the total demand from all household loads are measured continuously These loads will vary depending on ap...

Page 9: ...rned on when all controlled loads have been turned off by the 9312 but demand is still approaching the demand limit When this occurs you must either reduce the uncon trolled demand or increase the demand limit as suggested in the operating instructions Circuit On Indicators 6 These indicators when lit tell you which control points are enabled A Circuit On indication does not necessarily mean that ...

Page 10: ...ce will vary with the uniqueness of each house its occupants energy use and the utility s averaging period To arrive at the best demand setting for you requires some trial and error see Table 2 The 9312 has a demand limit setting range of 2 0 to 49 5 KW in 5 KW increments A good starting demand limit is 5 KW If you need more energy to maintain comfort increase the KW level by only 5 KW If after an...

Page 11: ...ning of each 1 minute interval This way Off Time of rotating loads is minimized The rotate strategy is particularly useful where equal priority rotation may serve several heating loads minimiz ing the Off Time of each load during rotation Thus the reduction in demand is shared by several loads and the 1 Press and hold Alarm Volume key 11 2 Simultaneously press the Decrease key 7 or the Increase ke...

Page 12: ...larly attractive feature because heat pump and air conditioning compressors requiring time delay switching may be controlled under a strategy to best fit your application lifestyle or use pattern The load shedding priority selected is based on the type of heating and cooling equipment and the design of your house If desired the priorities may be easily changed Priority 17 The 9312 allows the use o...

Page 13: ...ontrolling demand and it will increase the comfort level of your home Shifting use of all loads possible to Off Peak times will help to reduce your On Peak energy usage charge and increase your savings In most TOU Demand Rates the On Peak demand and energy charges are substantially more costly than the Off Peak charges Consult your utility to determine your On and Off Peak times Service of Heating...

Page 14: ... remains the same regardless of the number of Kwh s used Also called Flat Rate Under this rate demand is not measured recorded or billed Instantaneous Demand The electricity in kilowatts currently being drawn by the electrical service of a build ing at any instant in time Kilowatt KW 1 000 watts Kilowatt Hour Kwh The basic measurement of electric energy consumption as metered by the electric utili...

Page 15: ... d1 is displayed Release keys Temperature dE The current temperature in dE grees Fahrenheit inside the 9312 s C D Unit Day of Week do The current day of the week 1 Sunday 2 Monday 3 Tuesday 4 Wednesday 5 Thursday 6 Friday 7 Saturday Date Month Day dA The current month and day of the month Setting range from 1 1 to 12 31 Year Yr The current year Auto Daylight Saving Adjust dS Allows the 9312 to be ...

Page 16: ...g tells the 9312 how many relays are installed starting from Control Point 1 and counting up to 16 This setting turns off unused control points The number programmed into this setting should be equal to the number of relays and all relays should be on consecutive control points starting with 1 Only control points enabled at this setting will appear in subsequent settings for priorities Minimum On ...

Page 17: ... Start Time 12 00 a m 11 59 p m F2 Fall 1 End Time 12 00 a m 11 59 p m F3 Fall 2 Start Time 12 00 a m 11 59 p m F4 Fall 2 End Time 12 00 a m 11 59 p m Fd Fall Start Date 0 0 12 31 SS Saturday Sunday On Off Peak on oFF H1 Holiday 1 0 0 12 31 H2 Holiday 2 0 0 12 31 H3 Holiday 3 0 0 12 31 H4 Holiday 4 0 0 12 31 H5 Holiday 5 President s Day 0 0 12 31 oFFP onP H6 Holiday 6 Memorial Day 0 0 12 31 oFFP o...

Page 18: ...n Peak Demand Limit Period 6 2 0 49 5 o6 Off Peak Demand Limit Period 6 2 0 49 5 oFF oFF2 oFF3 oFF4 oFF5 d7 Start Date Period 7 0 0 12 31 L7 On Peak Demand Limit Period 7 2 0 49 5 o7 Off Peak Demand Limit Period 7 2 0 49 5 oFF oFF2 oFF3 oFF4 oFF5 d8 Start Date Period 8 0 0 12 31 L8 On Peak Demand Limit Period 8 2 0 49 5 o8 Off Peak Demand Limit Period 8 2 0 49 5 oFF oFF2 oFF3 oFF4 oFF5 d9 Start Da...

Page 19: ...stallation Manual 17 1 0 Introduction This manual contains instructions for the installation checkout and programming of the Energy Sentry 9312 Demand Management System In order to ensure proper installation and warranty coverage please read this manual thoroughly before proceeding with the installation Note All wiring must be installed in accordance with national and local electrical codes Import...

Page 20: ...s C D Unit will only recess in the wall correctly between studs because of the unit s depth 4 4 Drill screw holes first with 1 8 drill 4 5 Cut C D mounting hole with drywall knife being careful not to make it too large 4 6 Install the four C D Unit mounting clips P N 09000 02101 by pressing them onto the drywall in position over the mounting holes In most cases they should stay in place by themsel...

Page 21: ...s 2 voltage compartment This com partment is found on the right side of the relay box Aseparate conduit may also be required for the control cable 0 375 diameter 5 2 3 If installing an Expansion Relay Unit follow the pro cedure in paragraph 5 2 2 5 2 4 Vacuum out all dry wall dust metal chips wood chips and other foreign objects which may affect operation of the system 6 0 Running Control Cable Af...

Page 22: ...t the screw through the plastic housing through the hole in the short side of the C D Unit mounting clips through the drywall and into the small hole on the long side of the mounting clip The sheet metal screw will thread through the small hole and tighten the C D Unit enclosure to the wall Repeat this procedure with the other three screw s positions 8 4 When all four screws have been installed th...

Page 23: ...ng lug on the left side of the relay plate 10 5 Repeat instructions 10 2 through 10 4 for an Expanded Relay Unit Both Relay Units MUST be phased the same Caution Leave circuit breaker off until installation is complete 11 0 Installing Wiring Current Transformers Caution Installation of Current Transformers may need to be coordinated with the local utility company 11 1 Disconnect main power to the ...

Page 24: ...s with these types of heating systems the loads be connected as follows Example 1 Load Control Strategy Combination Circuit Load Priority 1 Dryer 1 2 Hot Water Heater 2 3 Heat 1 3 4 Heat 2 3 5 Heat 3 3 6 Heat 4 3 7 Heat 5 3 8 Heat 6 3 12 1 2 For Homes With Heat Pumps Without Compressor Connected Example Only In some heating climates it may be preferable not to connect the heat pump compressor to t...

Page 25: ... a short length of 10 or 12 AWG wire depending on circuit breaker size which runs into the Relay Unit Wire nut this length of wire to one lead of the relay s contact With another short length of the appropriately sized wire wire nut it to the other lead of the relay s contact Connect that same wire back to the circuit breaker s terminal where the first wire was originally removed as shown in Figur...

Page 26: ...ump com pressors to the Energy Sentry unit is normally accom plished by inserting a 3 Amp low voltage signal relay in series with the low voltage 24 VAC thermostat control loop as shown in Figure 10 Generalized Drawing This can be done in one of two ways 1 Use the low voltage relays on the Data Link PC Board for Circuits 2 and 3 or 2 Use remote low voltage relays Normally the relay is inserted in ...

Page 27: ...stem Checkout 17 1 Prior to Test a Turn off ALL circuit breakers in the circuit breaker panel b Turn on thermostats switches for controlled loads 17 2 Initial Operation Test a Ensure all circuit breakers in the circuit breaker panel are off b Turn on the 9312 circuit breaker c Control Display Unit should turn on beep once and light up with id showing in the Mode display If the unit fails to light ...

Page 28: ...nce all loads are shed the alarm will sound because the demand level is most likely still above the demand limit of 2 KW When this happens set the demand limit to its normal level apx 6 8 KW or whatever it may be for your specific home at that time of the year and the alarm should stop 17 6 Restore household loads to the desired condition The circuit breaker marked Energy Sentry or 9312 should be ...

Page 29: ..._________________________ ______________ mins on ____ off ____ 15 ___________________________________ ______________ mins on ____ off ____ 16 ___________________________________ ______________ mins on ____ off ____ Control Points 2 and 3 are shipped with 8 minutes on and 5 minutes off See Appendix B page for instructions Owner 1 Record circuit assignments above and in the space provided on the key...

Page 30: ...1 H2 7 4 Set Holiday Date 2 H3 12 25 Set Holiday Date 3 H4 0 0 Set Holiday Date 4 H5 onP Set Holiday Date 5 H6 onP Set Holiday Date 6 H7 onP Set Holiday Date 7 H8 onP Set Holiday Date 8 H9 onP Set Holiday Date 9 oP Reset Off Peak Peak Demand oL oFF Set Off Peak Demand Limit HL oFF Set High Instantaneous Limit nr 8 Set the Number of Relays Used Pr_1 1 Set Priority for Relay 1 Pr_2 2 Set Priority fo...

Page 31: ... Demand Limit Period 2 o2 oFF Set Off Peak Demand Limit Period 2 d3 0 0 Set Start Date Period 3 L3 6 Set On Peak Demand Limit Period 3 o3 oFF Set Off Peak Demand Limit Period 3 d4 0 0 Set Start Date Period 4 L4 6 Set On Peak Demand Limit Period 4 o4 oFF Set Off Peak Demand Limit Period 4 d5 0 0 Set Start Date Period 5 L5 6 Set On Peak Demand Limit Period 5 o5 oFF Set Off Peak Demand Limit Period 5...

Page 32: ...effect 4 Notification to BraydenAutomation Corporation or its authorized dealer under this warranty must be received within one week after discovering any defect in materials or workmanship 5 If the Energy Sentry Demand Management System is removed and returned to the authorized service dealer or Brayden Automation Corporation 6230 Aviation Circle Loveland CO 80538 for repair or replacement under ...

Page 33: ...Brayden Automation Corp 6230 Aviation Circle Loveland CO 80538 970 461 9600 FAX 970 461 9605 www brayden com P N 09312 94100A ...

Reviews: