The "relays/controls" menu
112
5.3.6
The "tariff control" submenu
!
Note!
The tariff control is only available for instruments with external limit switches
(FMU90-********B***).
The tariff control allows to define two different switch-on and switch-off points for each pump. An
external switch determines which of these switching points are currently valid. By connecting a
time switch to the Prosonic S this allows to use low priced tariff times preferentially for pumping.
"tariff control N" (N = 1 or 2)
"tariff control"
Determines if a tariff control is to be performed.
Selection:
• no (default)
• yes
"tariff input"
Allocates one of the switch inputs to the tariff control.
Selection:
• disabled
• ext. digin 1 (terminals 71, 72, 73)
• ext. digin 2 (terminals 74, 75, 76)
• ext. digin 3 (terminals 77, 78, 79)
• ext. digin 4 (terminals 80, 81, 82)
"tariff control N" (N = 1 or 2)
(pump selection)
Select the pump for which you are going to configure the tariff control from this list.
⇒
tariff control 1
R1607
tariff control:
tariff input:
⇒
tariff control 1
R1608
pump 1:
pump 2:
...