The "output/calculations" menu (for HART instruments)
127
6.2
The "extended calibration" submenu
6.2.1
"mode current N" (N = 1 or 2)
"current span"
Used to select the current span to which the measuring range is mapped.
Selection:
•
4-20 mA (default)
The measuring range (0%-100%) is mapped to the current range 4-20 mA.
•
0-20 mA
The measuring range (0%-100%) is mapped to the current range 0-20 mA.
•
fixed current HART
A fixed current is output. The value can be defined in the "mA value" parameter. The measured
value is transmitted by the HART signal.
L00-FMU90xxx-19-00-00-yy-066
A: current span = 4-20 mA; B: current span = 0-20 mA; C: current span = fixed current HART;
D: mA value
"mA value" (only available for "current span" = "fixed current HART")
Specifies the value of the fixed current.
• range of values: 3,6 - 22 mA
• default: 4 mA
⇒
mode current 1
OX202
current span:
output damping:
4mA threshold:
curr. turn down:
4
3.6
0
[mA]
20
[mA]
20
100 [%, ...]
0
-10
0
100 [%...]
0
[mA]
20
0
100 [%...]
A
B
C
D