The "relays/controls" menu
85
5.2.2
Overview
Parametrization of a pump control (type: limit control)
Step
Parameter set or submenu Parameter
Remarks
see section
1
"relay/controls" menu
Select "pump control1" or "pump control 2".
2
pump control N
(N = 1 or 2)
reference
Select the level according to which the pumps are controlled.
5.2.3
number of pumps
Select the number of pumps.
Note: A relay must be available for each of the pumps.
3
pump control N
(N = 1 or 2)
function
Select "limit control".
5.2.4
4
pump control N
(N = 1 or 2)
Select a pump.
(Each pump must be configured individually.)
5.2.5
5
pump M control N
(M = 1 - 6)
(N = 1 or 2)
switch on point
Define the switch on point for this pump.
5.2.6
switch off point
Define the switch off point for this pump.
switch on delay
Define the switch on delay for this pump.
alternate
Select if the pump is to take part in the alternating pump control (Default:
no).
crust reduction
Define the inaccuracy of the switching points (to reduce crust formation).
6
pump M control N
(M = 1 - 6)
(N = 1 or 2)
backlash interval
Define the backlash interval
5.2.7
backlash time
Define the backlash time
error handling
Define the error handling
7
relay allocation
Allocate a relay to the pump.
Note: By default, relay 1 is configured as alarm relay.
5.2.8
8
relay N
(N = 1 - 6)
function
Select "pump M/control N"
5.2.9
invert
Select if the switching signal is inverted (default: no)
9
pump control N
Select the next pump and continue with step 5 until all pumps have been
configured.
If all pumps are configured: Press
to return to the "relay/controls" menu.