The "level" menu
33
2.2
The "extended calibration" submenu
2.2.1
"LVL N distance mapping" (N = 1 or 2)
Is identical to the "LVL N distance mapping" parameter set in the "basic setup" submenu, see above.
2.2.2
"LVL N check value" (N = 1 or 2)
"correction"
This parameter can be used to shift the measured distance (between the sensor membrane and the
product surface) by a constant value. The distance entered into this parameter is added to the
measured distance.
2.2.3
"LVL N correction" (N = 1 or 2)
"offset"
This parameter can be used to shift the measured level by a constant value. The level entered into
this parameter is added to the measured level.
!
Note!
The level correction is applied before the linearisation.
2.2.4
"LVL N blocking distance" (N = 1 or 2)
"blocking distance"
Indicates the blocking distance of the respective sensor.
⇒
LVL1 check value
L1017
correction:
⇒
LVL1 correction
L1018
offset:
⇒
LVL1 block. dist.
L1019
blocking distance:
.