The "flow" menu
63
3.3.2
"totalizer N/daily counter N"
(N = 1 - 3)
"value"
Displays the current flow volume.
"overflow"
Whenever the counter passes the overflow, this parameter is incremented by 1. The total flow
volume thus is:
V
total
= overflow x 10
7
+ value
"reset" (only for the daily counters)
Use this parameter to reset the counter to "0".
Selection:
•
no (default)
"value" and "overflow" retain their values.
•
yes
"value" und "overflow" are reset to "0".
3.3.3
"totalizer N/daily counter N"
(N = 1 - 3)
"error handling"
Use this parameter to define the reaction of the Prosonic S in the case of an error.
Selection:
•
stop
The Prosonic S stops counting.
•
hold
The Prosonic S continues counting. It uses the flow value which was present at the moment the
error occured.
•
actual value
The Prosonic S continues counting. It uses the current flow value (although its reliability is no
longer ensured).
⇒
totalizer 1
F1203
value:
overflow:
⇒
totalizer 1
F1204
error handling: