The "flow" menu
45
The
"flow N state"
parameter set appears, in which the currently measured level, distance and
flow are displayed. Compare the displayed distance to the real distance in order to decide if a further
mapping is necessary.
If yes: Press the left-arrow key (
←
) in order to return to the "flow N mapping" parameter set.
If no: Press the right key (
→
) in order to return to the "flow N" submenu.
"status"
see below ("flow N status")
"flow N state" (N = 1 or 2)"
"level"
Displays the currently measured level.
"sensor"
Dispalys the currently measured distance between the sensor membrane and the liquid surface.
"flow N" (N = 1 or 2)
Displays the currently measured flow.
"status"
Use this parameter to define the status of the interference echo suppression.
•
enable map
Choose this option in order activate the interference echo suppression. The mapping is then used
for signal evaluation.
•
disable map
Choose this option in order to deactivate the interference echo suppression. The mapping is then
no longer used for signal evaluation but it can be reactivated if required.
•
delete map
Choose this option in order to delete the mapping. It can not be reactivated again and the
instrument uses the preprogrammed default mapping.
⇒
LVL1 state
L100C
level:
sensor:
flow N:
status: