Proline Promag W 500 PROFINET
Diagnostics and troubleshooting
Hauser
173
For system integration
Error
Possible causes
Solution
The device name is not displayed
correctly and contains coding.
A device name containing one or
more underscores has been
specified via the automation
system.
Specify a correct device name
(without underscores) via the
automation system.
12.2 Diagnostic information via light emitting diodes
12.2.1 Transmitter
Proline 500 – digital
Different LEDs in the transmitter provide information on the device status.
Power
I/O 2
I/O 3
I/O 3
1
2
3
4
5
3.
-
+
-
ESC
2.
Power
open
press
open
press
ESC
E
+
-
I/O 4
Power
I/O 2
I/O 3
1.
A0029689
1
Supply voltage
2
Device status
3
Flashing/network status
4
Port 1 active: PROFINET
5
Port 2 active: PROFINET and service interface (CDI)
1. Open the housing cover.
2. Remove the display module.
3. Fold open the terminal cover.
LED
Color
Meaning
1
Supply voltage
Off
Supply voltage is off or too low.
Green
Supply voltage is ok.
2
Device status (normal
operation)
Off
Firmware error
Green
Device status is ok.
Flashing green
Device is not configured.