Proline Promag W 500 PROFINET
Diagnostics and troubleshooting
Hauser
207
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
842 Process limit
Low flow cut off active!
1. Check low flow cut off configuration
• Flow velocity
• Mass flow
• Corrected volume flow
• Status
• Volume flow
Measured variable status [from the factory]
Quality
Uncertain
Quality substatus
Process related
Coding (hex)
0x78 to 0x7B
Status signal
S
Diagnostic behavior
Warning
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
882 Input signal
1. Check input configuration
2. Check external device or process
conditions
• Corrected conductivity
• Measured values 1
• Measured values 2
• Measured values 3
• Density
• Flow velocity
• Mass flow
• Coil current shot time
• Reference electrode
potential against PE
• Noise
• Reference density
• Corrected volume flow
• Temperature
• Status
• Volume flow
Measured variable status
Quality
Bad
Quality substatus
Maintenance alarm
Coding (hex)
0x24 to 0x27
Status signal
F
Diagnostic behavior
Alarm
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
937 Sensor symmetry
1. Eliminate external magnetic field near
sensor
2. Turn off diagnostic message
• Conductivity
• Corrected conductivity
• Density
• Electronic temperature
• Flow velocity
• Mass flow
• Coil current shot time
• Reference electrode
potential against PE
• Noise
• Reference density
• Corrected volume flow
• Temperature
• Status
• Volume flow
Measured variable status [from the factory]
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
S
Diagnostic behavior
Warning
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Summary of Contents for Proline Promag W 500