Proline Promag W 500 PROFINET
Commissioning
Hauser
153
Current output 1 to n simulation
Value current output 1 to n
Frequency output simulation 1 to n
Frequency value 1 to n
Pulse output simulation 1 to n
Pulse value 1 to n
Switch output simulation 1 to n
Switch status 1 to n
Relay output 1 to n simulation
Switch status 1 to n
Device alarm simulation
Diagnostic event category
Diagnostic event simulation
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry / User
interface
Factory setting
Assign simulation process variable
–
Select a process variable for
the simulation process that is
activated.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
Off
Process variable value
A process variable is selected
in the
Assign simulation
process variable
parameter
Enter the simulation value for
the selected process variable.
Depends on the
process variable
selected
0
Status input simulation 1 to n
–
Switch simulation of the status
input on and off.
• Off
• On
Off
Input signal level 1 to n
In the
Status input simulation
parameter, the
On
option is
selected.
Select the signal level for the
simulation of the status input.
• High
• Low
High
Current input 1 to n simulation
–
Switch simulation of the
current input on and off.
• Off
• On
Off
Value current input 1 to n
In the
Current input 1 to n
simulation
parameter, the
On
option is selected.
Enter the current value for
simulation.
0 to 22.5 mA
0 mA
Summary of Contents for Proline Promag W 500