Proline Promag W 500 PROFINET
Diagnostics and troubleshooting
Hauser
205
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
594 Relay output simulation
Deactivate simulation switch output
–
Measured variable status
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
C
Diagnostic behavior
Warning
12.7.4 Diagnostic of process
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
803 Current loop
1. Check wiring
2. Change I/O module
–
Measured variable status
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
F
Diagnostic behavior
Alarm
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
832 Electronic temperature too high
Reduce ambient temperature
• Conductivity
• Corrected conductivity
• Measured values 1
• Measured values 2
• Measured values 3
• Density
• Electronic temperature
• Flow velocity
• Mass flow
• Coil current shot time
• Reference electrode
potential against PE
• Noise
• Reference density
• Corrected volume flow
• Temperature
• Status
• Volume flow
Measured variable status [from the factory]
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
S
Diagnostic behavior
Warning
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.